inadequate vacuum obtained. The control has provisions to open the EXV for
refrigerant recovery and/or evacuation.
Set desired time period.
S
Default time period for procedure is 120 minutes.
d
Touch START on UI to open the valve.
S
Begin evacuation or refrigerant recovery as required for the procedure after
S
control indicates the EXV is open. Power may be removed from heat pump
after the control indicates "READY TO EVACUATE."
6.7.

Dealer Logo

Touch DEALER LOGO to upload the dealer logo and contact information from a
standard USB memory device connected to the Evolutionr Connex Control. The
"Dealer
Logo
Application"
www.HVACpartners.com is required to properly format the dealer logo and contact
information for use on the wall control.
Along with the dealer logo (if any), three lines of dealer information are provided
on the wall control:
Dealer name (50 characters, max)
Dealer phone number (20 characters, max)
Dealer URL (50 characters, max)
The wall control dealer information display is 30 characters wide. Dealer names
and URLs over 30 characters will be split into two lines on the display.
PC/MAC
software
54
download
available
on