50XL RIGGING WEIGHTS
DETAIL
A

SELECTION PROCEDURE

Determine cooling and heating requirements at design
conditions:
Given:
REQUIRED COOLING CAPACITY (TC)
SENSIBLE HEAT CAPACITY (SHC)
REQUIRED HEATING CAPACITY (SHC)
CONDENSER ENTERING AIR TEMPERATURE 95°F (35°C)
INDOOR- -AIR TEMPERATURE
(19.4°C) EWB
EVAPORATOR AIR QUANTITY
ELECTRICAL CHARACTERISTICS
Select unit based on required cooling capacity
Enter Net Cooling Capacities table at condenser entering
temperature of 95°F (35°C). The 036 unit at 1200 cfm and 67°F
(19.4°C) ewb (entering wet bulb) will provide a total capacity of
34,600 Btuh and a SHC of 24,220 Btuh. Calculate SHC correction,
if required, using Note 4 under Cooling Capacities tables.
-in. (914 mm)
A06298
Fig. 4 - - Suggested Rigging
. . . . . .
34,500 BTUH
. . . . . . . . .
24,000 BTUH
. . . . .
15,000 BTUH
. . .
80°F (26.6°C) EDB, 67°F
. . . . . . . . . . . . . . .
1200 CFM
. . . . . . . . . . . . .
230- -1- -60
CABINET
Small
Large
NOTE: See dimensional drawing for corner weight distribution. Corner
weights shown on drawing are based on unit---only weights and do not
include packaging.
Select electric heat
The required heating capacity is 15,000 Btuh.
Determine additional electric heat capacity in kW.
15,000 Btuh
3414 Btuh/kW
= 4.4kW of heat required
Enter the Electric Heater table on page 5 for 208/230v,
single- -phase unit. The 5- -kW heater at 240v most closely satisfies
the heating required. To calculate kW at 230v, multiply the heater
kW by multiplication factor 0.92 found in the Multiplication
Factors table on page 17.
5 kW x 0.92 = 4.6 kW
4.6 kW x 3414 Btuh/kW = 15,704 Btuh (Total unit heating
capacity)
Select unit that corresponds to power source available
The Electrical Data table shows that the unit is designed to operate
at 208/230- -1- -60.
10
A06296
RIGGING WT
MODEL
lb
kg
50XL- -024
382
173
50XL- -030
387
176
50XL- -036
469
213
50XL- -042
491
223
50XL- -048
497
225
50XL- -060
548
249

Hide quick links: