PERFORMANCE DATA
PERFORMANCE TEST
All data based upon listed indoor dry bulb temperature. .00
inches external static pressure on coil of outdoor section.
Indoor air cubic feet per minute (CFM) as listed in the Perfor-
mance Data Sheets:
If conditions vary from this, results will change as follows:
1. As indoor dry bulb temperatures increase, a slight
increase will occur in indoor air temperature drop (Delta
T). Low and high side pressures and power will not
change.
2. As indoor CFM decreases, a slight increase will oc-
cur in indoor temperature drop (Delta T). A slight de-
crease will occur in low and high side pressures and
power.
A properly operating unit should be within plus or minus 2
degrees of the subcooling value shown in the Heat Pump
Specifications.
A properly operating unit should be within plus or minus 3
degrees of the typical (Delta T) value shown.
A properly operating unit should be within plus or minus 7
36
Model: SSZ140361B* / AR*F374316B*+TXV -1
Conditions: 1250 CFM Indoor Air @ 70°F DB
Basic U nit without
Outdoor
Auxiliary Heat
Ambient
capacity
°F.
btuh
c.o.p.
65
41.48
4.11
60
39.27
3.96
55
36.96
3.80
34.55
3.62
50
45
31.98
3.41
40
29.70
3.23
35
27.39
3.04
24.92
2.49
30
25
23.00
2.35
20
21.18
2.21
15
19.26
2.06
17.28
1.89
10
15.32
1.72
5
0
13.36
1.53
-5
11.40
1.34
-10
9.34
1.13
Capacity of U nit*
With KW of Auxiliary heat
4.8
9.6
14.4
57.86
74.24
90.63
107.01
55.65
72.03
88.42
104.80
53.34
69.72
86.11
102.49
50.93
67.31
83.70
100.08
48.36
64.74
81.13
97.51
46.08
62.46
78.85
95.23
43.77
60.15
76.54
92.92
41.30
57.68
74.07
90.45
39.38
55.76
72.15
88.53
37.56
53.94
70.33
86.71
35.64
52.02
68.41
84.79
33.66
50.04
66.43
82.81
31.70
48.08
64.47
80.85
29.74
46.12
62.51
78.89
27.78
44.16
60.55
76.93
25.72
42.10
58.49
74.87
PSIG of the HI PR shown.
A properly operating unit should be within plus or minus 3
PSIG of the LO PR shown.
A properly operating unit should be within plus or minus 3
Amps of the typical value shown.
NOTE: Pressures are measured at the liquid and suction
service valve ports.