CONDENSING UNIT SPECIFICATIONS
GSC130[42-60]1*
Nominal Cooling Capacity, BTUH
Compressor
R.L. Amps
L.R. Amps
Condenser Fan Motor
Horsepower
F.L. Amps
Refrigerant Line Size
Liquid Line, Inches O.D.
Suction Line, Inches O.D.
Refrigerant Connection Size
Liquid Valve Size O.D.
Suction Valve Size O.D.
Refrigerant Charge
Power Supply
(1)
Minimum Circuit Ampacity
Maximum Overcurrent Device
Electrical Conduit Size
Power Supply (Inches)
Approximate Shipping Weight
(1)
Wire size should be determined in accordance with National Electrical Codes; extensive wire runs will require larger wire sizes.
(2)
Maximum Overcurrent Protection Device:
MUST use Time Delay Fuse or HACR type Circuit Breaker of the same size as noted.
(3)
Installer will need to supply 3/4" to 7/8" adapters for suction line connectors
(4)
Installer will need to supply 7/8" to 1-1/8" adapters for suction line connections.
NOTE: This data is provided as a guide, it is important to electrically connect the unit and properly size fuses/circuit
breakers and wires in accordance with all national and/or local electrical codes. Use copper wire only.
GSC130421BB GSC130481BB GSC130601CB
42,000
19.2
104
1/4
1.5
3/8"
1-1/8"
3/8"
4
7/8"
95
208/230-60-1
208/230-60-1
25.5
(2)
40
1/2 or 3/4
199
48,000
57,000
17.9
19.9
104
137
1/4
1/4
1.5
1.5
3/8"
3/8"
1-1/8"
1-1/8"
3/8"
3/8"
4
4
7/8"
7/8"
102
131
208/230-60-1
23.9
26.4
40
45
1/2 or 3/4
1/2 or 3/4
210
242
GSC130[42-60]1*
7