FCS-320-TM Aspirating Smoke Detector
6.7.1

Preparations for the Functional Test

9.
NOTICE!
Once the pipe system has been disconnected from the FCS-320-TM, the device reports a
malfunction when the set airflow malfunction delay has elapsed. If no airflow malfunction is
detected, the device is faulty.
Figure 6.2 Checking the pipe system connection
10. Connect the test pipe.
11. Connect the pressure measuring hose to the adapter connection B. When carrying out a
12. Connect the 4-pin plug of the adapter to the digital pressure gauge.
13. Connect the PC to the FCS-320-TM through the diagnostic appliance and start the
Bosch Sicherheitssysteme GmbH
Disconnect the pipe system from the FCS-320-TM.
3.
4
B
A
limited functional test without a digital precision pressure gauge, the connection for the
pressure measuring hose on the test pipe must be closed.
diagnosis program.
Operation Guide
1
2
ø 4,6 mm
ø 4,2 mm
ø 7,0 mm
4.
3
5.
5
Commissioning | en
1
Test pipe
2
Aspiration borings
3
Pressure measuring hose
4
Adapter
5
Digital precision pressure
gauge
A/
Adapter connection
B
F.01U.130.928 | 1.0 | 2009.11
81