74
en | Installation of the Pipe System
5.8

water separator

Standard
The standard water separator is installed using a PG29 screw connection and a T-piece
between the FCS-320 and the pipe system.
FAS-ASD-WS Water Separator
The FAS-ASD-WS Water Separator must be fitted at the lowest point in the pipe system
downstream of the air filter and the aspirating smoke detector (see Figure 5.9).
Figure 5.9 Installing the FAS-ASD-WS Water Separator in the pipe
system
Connection
Attach two 45° pipe elbows on both sides (not supplied as standard) in order to achieve the
optimum distance from the wall for mounting the brackets. When installing, note the correct
direction of flow (see arrow on plastic container).
Also fasten the water separator with two screws and the clamp.
To empty, open the drain valve (see Section 7.12 Maintenance Intervals, page 93).
F.01U.130.928 | 1.0 | 2009.11
2
1
3
Operation Guide
FCS-320-TM Aspirating Smoke Detector
1
2
3
3
water separator
Pipe system connection
45° pipe elbow
Bosch Sicherheitssysteme GmbH