FCS-320-TM Aspirating Smoke Detector
I pipe system activation thresholds
I-pipe system
Activation threshold
0 not practical
Example:
If 2 of a total of 5 air sampling openings are found to be obstructed, airflow monitoring must
be set to ± 20% using the FAS-ASD-DIAG Diagnostic Software.
NOTICE!
When planning in accordance with EN 54-20, airflow monitoring must always be set to 20%.
3.7.2

U-pipe system

1 pipe system
FCS-320-TM
FCS-320-TM-R
Min. distance FCS-320-TM – 1st air sampling opening
Max. distance FCS-320-TM – 1st air sampling opening
max. branch length
Max. total pipe length per pipe system
Max. total pipe length per pipe system for a fan voltage < 10.5 V
Min. distance between 2 air sampling openings (d)
Max. distance between 2 air sampling openings (d)
Max. number of air sampling openings (n) per pipe system
Bosch Sicherheitssysteme GmbH
Number of obstructed air
sampling openings
1 obstructed opening
2 obstructed openings
3 obstructed openings
4 obstructed openings
5 obstructed openings
Figure 3.8 U-pipe system for space protection
Pipe Ø 25 mm
Additional pipe Ø 12 mm
Pipe Ø 25 mm
Additional pipe Ø 12 mm
Operation Guide
Number of air sampling openings
2
± 30%
0
0
0
0
FAS / FCS
A
B
Planning | en
3
4
5
± 20%
± 15%
± 10%
0
± 30%
± 20%
0
0
0
0
0
0
0
0
0
C
D
2 m
20 m
25 m
50 m
8 x 3 m
40 m
8 x 3 m
4 m
10 m
8 units
F.01U.130.928 | 1.0 | 2009.11