en | Installing the Aspirating Smoke Detector
4.4.4

Connecting the relay board

1
2
3
4.5

Settings via the FAS-ASD-DIAG Diagnostic Software

fire source identification
NOTICE!
The term "ROOM·IDENT" is used in the FAS-ASD-DIAG Diagnostic Software for the
identification of the fire source.
Fire source identification is activated/deactivated using the FAS-ASD-DIAG Diagnostic
Software via the "Settings" screen. The "ROOMIDENT" function is deactivated as standard.
4.5.1

Setting the Response Sensitivity

The sensitivity of the detection unit can be adjusted via FAS-ASD-DIAG.
Detection unit
F.01U.130.928 | 1.0 | 2009.11
1
3
X1
FCS-320-TM-HB
To next board
Relay board
Sensitivity
0.5-2%/m
Operation Guide
FCS-320-TM Aspirating Smoke Detector
+24V
1a
1b
0V
2a
2b
3a
3b
4a
4b
5a
5b
6a
6b
7a
7b
8a
8b
2
X8
X2
X3
Standard sensitivity
0.5 %/m
X9
X4
X5
Setting intervals
0.1 %/m