en | Planning
3.5

Planning Limits

The following limiting values must always be observed for the FCS-320-TM series:
Limiting values Maximum monitoring area per air sampling opening
Maximum number of air sampling openings per pipe
system
Maximum number of air sampling openings per pipe
system with fire source identification
Maximum pipe length per pipe system
Pipe ∅ 25 mm
Additional pipe ∅ 12 mm
Maximum total monitoring area per pipe system
Minimum pipe length between 2 air sampling openings
Minimum pipe length between 2 air sampling openings
with fire source identification
Minimum pipe length between 2 air sampling openings
1
Plans not contained in the operation guide must be requested
2
Depending on the selected plan, some restricted values may apply
The maximum total monitoring area of the FCS-320-TM and the maximum total pipe length
depend on the plan selected (see Section 3.6 Standard Pipe Planning).
NOTICE!
The planning limits specified in this operation guide may be restricted in line with country-
specific regulations.
F.01U.130.928 | 1.0 | 2009.11
1
2
Operation Guide
FCS-320-TM Aspirating Smoke Detector
Corresponds to the maximum
monitoring range for point detectors,
in line with applicable national norms.
8
5
50 m
8 x 3 m
400 m²
0.1 m
3 m
10 m