Diagnostics
Table 40. Observing signal strength on the sensor
(wireless controls)
LED state
User action
(WZS sensors)
None
LED1: Off
LED2: Off
LED3: Off
Press Test
LED1: Off
button on the
LED2: Off
sensor
LED3: Off
LED1: On
LED2: On
LED3: On
Displays for 5
seconds, then
constantly Off
LED1: Off
LED2: On
LED3: On
Displays for 5
seconds, then
constantly Off
LED1: Off
LED2: Off
LED3: On
Displays for 5
seconds, then
constantly Off
Table 41. Observing signal strength on the receiver
(wireless controls)
User
LED state (receiver, all
action
models)
None
LED1: Off
LED2: Off
LED3: Off
Press
LED1: On
Test
LED2: On
button
LED3: On
on the
Displays for 5 seconds, then
sensor
constantly Off
LED1: Off
LED2: On
LED3: On
Displays for 5 seconds, then
constantly Off
LED1: Off
LED2: Off
LED3: On
Displays for 5 seconds, then
constantly Off
Testing Battery Status (Wireless Controls)
Initiate a battery status test as follows:
On model WZS, push the Test button on the sensor (see
location on
Figure 62, p.
responds by indicating the level of battery strength, as
shown in
Table 42, p.
96
Symbol (WDS
sensor
display)
Indicates...
No Test symbols
Normal state
appear
• No Test button press.
Associated; no
communication with
receiver
• Associated, but no
signal from the
receiver after
pressing Test button.
Excellent signal
strength
• Good signal margin
for reliable
communication.
Satisfactory signal
strength
• Adequate signal
strength for reliable
communication.
• Moving sensor or
receiver may improve
signal strength.
• Increased channel
switching may reduce
battery life.
Poor signal strength
• Unreliable
communication.
• Strongly recommend
moving the sensor or
receiver to a better
location.
Indicates...
Normal state
• No Test button press.
Excellent signal strength
• Good signal margin for reliable
communication.
Satisfactory signal strength
• Adequate signal strength for
reliable communication.
• Moving sensor or receiver may
improve signal strength.
• Increased channel switching may
reduce battery life.
Poor signal strength
• Unreliable communication
• Strongly recommend moving the
sensor or receiver to a better
location
95). LED5 on the sensor
96.
On model WDS, push the Test button on the sensor
(see location on
Figure 62, p.
test symbol appears on the display. The symbol shown
indicates battery life expectancy (see
Table 42. Battery status: LED5 on model WZS sensors
(wireless controls)
User
action LED state (WZS)
Press
Solid green for 5 seconds Battery is adequate for proper
Test
button
Solid red for 5 seconds
No light
None
Blinking red: 1-blink
(a)
pattern
repeated 5
times. Cycle repeats
every 15 minutes.
(a) Blink pattern is On for 1/4 s, Off for 3/4 s, with 2 s Off between repe-
titions.
Table 43. Battery status: Battery symbol on model WDS
sensor display (wireless controls)
Battery
User
test
action
symbol
Indicates...
Press Test
Full battery power.
button
50% battery life left.
25% battery life left. Replace batteries.
Flashing symbol indicates that approximately 14
days of operation remain before the battery is too
weak to power the sensor.
24 V Power Status Indicator (Wireless Controls
LED5 on the receiver of all models
and stays constantly On when 24 V power is normal.
Using the Wireless Sensor System to Check
Signal Strength on a Site (Wireless Controls)
Follow these steps to check the signal strength on a site:
1. Power up a receiver with a 24 V transformer (user
supplied)
2. Associate the sensor to a receiver of the same model
intended for the job
3. Place the receiver at the desired location
4. Place or hold the sensor at the desired location
5. Press the Test button (S5) on the sensor and observe
the signal strength as indicated by LED1, LED2, and
LED3 on model WZS, and on the display on model
WDS
(Figure 62, p.
95).
95). In response, a battery
Table
43).
Indicates...
operation.
25% battery life left. Batteries should
be replaced.
Batteries life expired or not installed
properly, or sensor is defective.
Approximately 14 days of operation
remain before the battery is too weak
to power the sensor.
(Figure 61, p.
94) lights
UV-SVN02C-EN