Model Q Sizes 16 through 60 Super Q II Fans Sizes 16 through 44 Model Q Fans Sizes 16 through 60 FAN-DS-2 August 2000 ™ Fans Super Q II Fans Sizes 16 through 44...
1, 2 and 3. Arrangement 9 permits factory mounting of the motor on top, bottom, or either side of the fan — see below. AMCA Licensed Ratings The Trane Company certifies that the Model Q fans shown herein are licensed to bear the AMCA Seal.
Page 3
Double acoustic enhancement — insulation and perforated sheet metal to attenuate radiated sound • Fan insulation — self-adhesive foam, applied on the outside of the fan shell to protect against moisture • Variable frequency inverter balancing and reinforcement (frequency inverter by others).
Page 4
Trane Model Q ™ compact fan. The shaded area represents range of vaneaxials tested. Trane Model Q fans require up to 85 percent less cubic space than airfoil centrifugal fans and 40 percent less than common vaneaxials of equivalent installed sound level.
Page 5
Variable Air Volume Compatible The Super Q fan is modulated for VAV with variable frequency drives (by others), not with inlet vanes. Variable speed inverter fan modulation offers exceptional energy saving and exceptionally quiet part load operation.
Page 6
It provides proven acoustical performance with less design risk. In project after project, the Trane Model Q fan has been the key to creating NC 15 to NC 35 quiet comfort jobs. Beyond quiet, the Super Q II Plus system is small and compact.
Page 7
[7] Hub Streamlining Insulation [12] End Cone [8] Exact Blade to Vane Spacing [11] Precise Divergent Angle Diffuser Discharge Cone Precision cast fan wheel and diffuser for highly efficient aerodynamic performance. [8] Note: Call-out numbers shown above are referenced on page 8. Features...
Page 8
Benefits The aerodynamically shaped inlet bell [2] and inlet cone [3] provide uniform axial flow parallel to the fan shaft. Air is delivered equally to the leading edge of the fan blades — no crowding toward the fan tips.
Page 9
Because of its size and weight, it is floor mounted and connected to a return air plenum. In contrast, a 44-inch Model Q fan is used in Figure F-2 instead of a centrifugal fan. Its smaller size and lighter weight permits ceiling suspension and approximately 75 sq ft of floor space is freed up for other use.
Page 10
Blow-Thru Supply Application Figure F-7 shows a typical medium pressure, built-up, blow-thru system. The fan, enclosed in a plenum, is a 33- inch, double width, airfoil centrifugal that delivers 30,000 cfm of air. The bulkiness of the plenum is dictated by the necessary clearances around the fan.
Page 11
Install Isolation Average Total Installed Cost Comparison is based on equal size fans of similar capacities. The airfoil centrifugal fan is used as base (100%) for comparative purposes. Figures are based on estimates by experienced installing contractors. Arrangement 9 Trane Model Q fan...
Page 12
Field supplied motor & field •mounted TRES Thrust restraints WB (direct ship) NONE No thrust restraints DUCT Duct canvas WBAL FACT Q fan inverter factory balancing FIELD Inverter ready balanced by customer Model Number Description Valid Select- Prod. able Cat.
Page 13
0.075 lbs/ft at 70 F and a barometer reading of 29.92- inches Hg) The System An air system may consist of a fan, ductwork, air control dampers, cooling coils, heating coils, filters, diffusers, noise attenuation, turning vanes, etc. The fan is the component in the system...
Page 14
Performance Data Determination The fan performance section of this catalog contains a fan performance table and fan curve for each fan size. The performance data contained in this catalog was calculated from tests conducted in accordance with AMCA Standard 210 Laboratory Methods of Testing Fans for Rating.
Page 15
Isolates fan *Note: Bellmouth effect included in unducted installation Kt correction. Fan sizes 49 through 60 fan curves are cataloged with inlet bells. For unducted inlets without bells on size 49 through 60 fans add .1 to the inlet Kt given above.
Page 16
Magnetek low noise inverter drives and Century high efficiency motors for optimum modulation performance. Operating the Q or Super Q II fan on AC frequency drives requires the Q fan to be strengthened and balanced in the factory. This option “beefs up” the...
Page 17
40 percent wocfm, whichever is greater. Forty percent wocfm is the minimum point a Q fan with inlet vanes can modulate, due to inherent instability that results when the vanes close to a certain angle.
Page 18
Minimizing belt tension forces increases bearing life and reduces fan noise. The Q fan and Super Q II fan drive selection is totally computerized by the factory to achieve quiet, long life operation. If Trane provides Q fan...
Page 19
Operating Cost/Efficiency The quiet Q fan is a very efficient fan. The Q fan mixed-flow type airfoil thrust blades offer outstanding efficiency and operating cost savings over such fan types as plug fans. Designers can compare the Q fan efficiency with other...
Page 20
Trane Q fans are designed to be used in any installation where a standard airfoil centrifugal fan can be used. The sound level of the Q fan in the difficult to attenuate lower frequencies is lower than that produced by standard airfoil centrifugal fans with the same capacity.
63 Hz 125 HZ 250 Hz 500 Hz *Approximate attenuations. Use the Trane Fan Selection Program for attenuation predictions that include silencer regenerated self-noise. NOTE: Super Q II not available with Class III fans. If inlet vane modulation was selected, increase the rpm by 1 percent and increase the bhp by 3 percent.
Page 22
Power rating (BHP) does not include drive losses. Performance ratings do not include the effects of appurtenances in the airstream. When inlet vanes are used increase rpm 1 percent and brake horsepower 3 percent. Fan tables cover part of fan operating range; fan curves show full operating range. Performance...
Page 23
1.5 - 5 5 - 15 — 5 - 15 Q Fan and Super Q II Size 16 Super Q Fan Size 16” Min - Max Min - Max Motor HP Motor HP Class 1 Class 2 1 - 2...
Power rating (BHP) does not include drive losses. Performance ratings do not include the effects of appurtenances in the airstream. When inlet vanes are used increase rpm 1 percent and brake horsepower 3 percent. Fan tables cover part of fan operating range; fan curves show full operating range. Performance...
Page 25
3 - 7.5 7.5 - 15 — 7.5 - 15 Q Fan and Super Q II Size 19 Super Q Fan Size 19” Min - Max Min - Max Motor HP Motor HP Class 1 Class 2 1 - 3...
Page 26
Power rating (BHP) does not include drive losses. Performance ratings do not include the effects of appurtenances in the airstream. When inlet vanes are used increase rpm 1 percent and brake horsepower 3 percent. Fan tables cover part of fan operating range; fan curves show full operating range. Performance...
Page 27
3 - 10 10 - 15 — 10 - 15 Q Fan and Super Q II Size 21 Super Q Fan Size 21” Min - Max Min - Max Motor HP Motor HP Class 1 Class 2 1 - 5...
Page 28
Power rating (BHP) does not include drive losses. Performance ratings do not include the effects of appurtenances in the airstream. When inlet vanes are used increase rpm 1 percent and brake horsepower 3 percent. Fan tables cover part of fan operating range; fan curves show full operating range. Performance...
Page 29
Class 3 5 - 15 15-30 — 15 - 30 Q Fan and Super Q II Size 24 Super Q Fan Size 24” Min - Max Min - Max Motor HP Motor HP Class 1 Class 2 1 - 5...
Page 30
Power rating (BHP) does not include drive losses. Performance ratings do not include the effects of appurtenances in the airstream. When inlet vanes are used increase rpm 1 percent and brake horsepower 3 percent. Fan tables cover part of fan operating range; fan curves show full operating range. Performance...
Page 31
5 -15 15 - 40 5 -15 15 - 40 Q Fan and Super Q II Size 27 Super Q Fan Size 27” Min - Max Min - Max Motor HP Motor HP Class 1 Class 2 1 - 7.5...
Page 32
Power rating (BHP) does not include drive losses. Performance ratings do not include the effects of appurtenances in the airstream. When inlet vanes are used increase rpm 1 percent and brake horsepower 3 percent. Fan tables cover part of fan operating range; fan curves show full operating range. Performance...
Page 33
7.5 - 20 15 - 50 7.5 - 20 15 - 50 Q Fan and Super Q II Size 30 Super Q Fan Size 30” Min - Max Min - Max Motor HP Motor HP Class 1 Class 2 1 - 7.5...
Page 34
Power rating (BHP) does not include drive losses. Performance ratings do not include the effects of appurtenances in the airstream. When inlet vanes are used increase rpm 1 percent and brake horsepower 3 percent. Fan tables cover part of fan operating range; fan curves show full operating range. Performance...
Page 35
7.5 - 25 20 - 50 7.5 - 25 20 - 60 Q Fan and Super Q II Size 33 Super Q Fan Size 33” Min - Max Min - Max Motor HP Motor HP Class 1 Class 2 1 - 10...
Page 36
Power rating (BHP) does not include drive losses. Performance ratings do not include the effects of appurtenances in the airstream. When inlet vanes are used increase rpm 1 percent and brake horsepower 3 percent. Fan tables cover part of fan operating range; fan curves show full operating range. Performance...
Page 37
10 - 30 25 - 50 10 - 30 25 - 75 Q Fan and Super Q II Size 36 Super Q Fan Size 36” Min - Max Min - Max Motor HP Motor HP Class 1 Class 2 1.5 - 15...
Page 38
Power rating (BHP) does not include drive losses. Performance ratings do not include the effects of appurtenances in the airstream. When inlet vanes are used increase rpm 1 percent and brake horsepower 3 percent. Fan tables cover part of fan operating range; fan curves show full operating range. Performance...
Page 39
10 - 40 30 - 50 10 - 40 30 - 75 Q Fan and Super Q II Size 40 Super Q Fan Size 40” Min - Max Min - Max Motor HP Motor HP Class 1 Class 2 1.5 - 15...
Page 40
Power rating (BHP) does not include drive losses. Performance ratings do not include the effects of appurtenances in the airstream. When inlet vanes are used increase rpm 1 percent and brake horsepower 3 percent. Fan tables cover part of fan operating range; fan curves show full operating range. Performance...
Page 41
15 - 40 40 - 50 15 - 40 40 - 75 Q Fan and Super Q II Size 44 Super Q Fan Size 44” Min - Max Min - Max Motor HP Motor HP Class 1 Class 2 3 - 20...
Page 42
Performance ratings do not include the effects of appurtenances in the airstream. When inlet vanes are used increase rpm 1 percent and brake horsepower 3 percent. Fan tables cover part of fan operating range; fan curves show full operating range. Performance...
Page 43
Min - Max Motor HP Motor HP Class 2 Class 3 20 - 50 — — — Q Fan Size 49 Super Q Fan Size 49” Min - Max Min - Max Motor HP Motor HP Class 1 Class 2...
Page 44
Performance ratings do not include the effects of appurtenances in the airstream. When inlet vanes are used increase rpm 1 percent and brake horsepower 3 percent. Fan tables cover part of fan operating range; fan curves show full operating range. Performance...
Page 45
Min - Max Motor HP Motor HP Class 2 Class 3 20 - 60 — — — Q Fan Size 54 Super Q Fan Size 54” Min - Max Min - Max Motor HP Motor HP Class 1 Class 2...
Page 46
Performance ratings do not include the effects of appurtenances in the airstream. When inlet vanes are used increase rpm 1 percent and brake horsepower 3 percent. Fan tables cover part of fan operating range; fan curves show full operating range. Performance...
Page 47
Min - Max Motor HP Motor HP Class 2 Class 3 25 - 75 — — — Q Fan Size 60 Super Q Fan Size 60” Min - Max Min - Max Motor HP Motor HP Class 1 Class 2...
Page 48
Dimensional Data and Weights Roughing-In Dimensions Arrangement 9 Arrangement 9 Dimensions Size Class I Class II Class III Class I Class II Class III Class I Class II Class III Class I Class II Class III Class I Class II Class III Class I Class II...
Page 49
Dimensional Data and Weights Roughing-In Dimensions Arrangement1 Arrangement 1 Dimensions Size Class III Class III Class III Class III Class II Class III Class II Class III Class I Class II Class III Class I Class II Class III Class I Class II Class III Class I...
Page 50
Dimensional Data and Weights Roughing-In Dimensions Arrangement 9 Arrangement 9 Dimensions Size Class I Class II Class I Class II Class I Class II Approximate weights are without motor and drive. Drive Unit Shaft Net Wt. Max. Dia. Lbs. 1020 1075 1090 1140...
Figure D-1 — Q Fan Inlet Vanes Figure D-2 — Q Fan Duct Outlet Diffuser, Sizes 16-44 Dimensional Data and Weights ½” 1” Q Fan Accessory Dimensions Table D-1 — Inlet Vane Dimensions Number Approx. Fan Size of blades Wt. Lbs.
Page 52
Figure D-3 — Super Q II 16-44 Sizes Table D-3 Unit Size * Approximate weights are without motor and drive. Dimensional Data and Weights Inlet Area Outlet Area Sq. Ft. Sq. Ft. 11.6 10.6 14.9 12.6 Q Fan Accessory Dimensions Unit Weights* 1048 1375 1567 1858...
Page 53
D-4 — Q Fan/Super Q II Plus Outlet Silencers Figure D-5 — Q Fan/Super Q II Plus Inlet Silencers Dimensional Data and Weights Table D-4 — Short Outlet Plus Silencer Approx. Size Weight 16” 18” 26” 18” 19” 20”...
Page 54
Hydraulically expanded stiffening ring welded in area of wheel raceway. On VAV variable speed fan units, fan inlet supports are structurally reinforced to handle extra stresses of variable speed fan modulation and fan is balanced at ten different fan speeds over the desired operating range.
Page 55
Heavy-gauge steel wire mesh. Inlet Bellmouth (Q, SQ2) On unducted inlets, the radius bellmouth uniformly accelerates air into the fan, reducing noise and energy requirements. Plus Duct Silencer (Q, SQ2) Significantly attenuates fan airborne sound levels. Center body of round silencer is dimensional matched to Q-fan hub.
Page 56
An American Standard Company www.trane.com For more information contact your local sales office or e-mail us at comfort@trane.com Since The Trane Company has a policy of continuous product improvement, it reserves the right to change design and specification without notice. Library Product Literature...