Trane HUV Installation, Operation And Maintenance Manual page 95

Horizontal unit ventilator
Table of Contents

Advertisement

Figure 62. LED, Test button, and symbol locations on
the sensor
LED1
LED2
LED3
LED5
Test button
WZS sensor
Test symbols
Error code
Test button
WDS sensor
Diagnostics (Wireless Controls)
LED1, LED2, and LED3, located on the sensor of model
WZS respond to diagnostics by exhibiting specific blinking
patterns. View their response by pressing the Test button
(see
Table 38, p.
95).
UV-SVN02C-EN
.
Error codes appear on the display of the model WDS
sensor when diagnostics occur (see
Table 38. Diagnostics on the sensor (wireless controls)
Error code
LED state when Test
(WDS
button is pressed (WZS
sensor
sensor)
display)
N/A
E0, E5, E7
LED1: Off
E1
LED2: Off
(a)
LED3
: 1-blink pattern
repeated 3 times
LED1: Off
E2
LED2: Off
(a)
LED3
: 2-blink pattern
repeated 3 times
LED1: Off
E3
LED2: Off
(a)
LED3
: 3-blink pattern
repeated 3 times
LED1: Off
E4
LED2: Off
(a)
LED3
: 4-blink pattern
repeated 3 times
(a) Blink pattern is On for 1/4 s, Off for 1/4 s, with 2 s Off between repe-
titions.
LED1, LED2, and LED3, located on the receiver of all
models, respond to diagnostics by exhibiting specific
blinking patterns. They respond independently of any user
action (see
Table
39).
Table 39. Diagnostics on the receiver (wireless controls)
LED state
Indicates...
LED1: Off
Disassociated
LED2: Off
• Receiver is not associated, waiting for a
LED3: 1-blink pattern
sensor.
(a)
repeated continuously
• Receiver lost communication with sensor.
• Receiver has no devices on its wireless
personal area network.
• Association with a device has been
manually removed.
LED1: Off
Address set to 000
LED2: Off
• Address not set to between 001–999.
LED3: 2-blink pattern
(a)
repeated continuously
LED1: Off
Not configured
LED2: Off
• Receiver configuration properties not
LED3: 3-blink pattern
properly set (defective receiver).
(a)
repeated continuously
(a) Blink pattern is On for 1/4 s, Off for 1/4 s, with 2 s Off between repe-
titions.
Testing Signal Strength (Wireless Controls)
To initiate a signal strength test, push the Test button on
the sensor (see location of Test button in
Models WZS: LED1, LED2, and LED3 respond by
indicating signal strength. You can view them on the
sensor
(Table
40) and the receiver
Model WDS: Test symbols on the sensor display
indicate signal strength
LED3, on the receiver, respond by indicating signal
strength
(Table
41).
Diagnostics
Table
38).
Indicates...
Sensor failure
• Replace sensor
Disassociated
• Sensor is not associated with
a receiver.
Address set to 000
• Address not set to between
001–999.
Software error
• Replace sensor
Input voltage too high
• No RF transmission is
permitted with an input
battery voltage greater than
3.9 V.
Figure
62).
(Table
41).
(Table
40). LED1, LED2, and
95

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Huvc

Table of Contents