Troubleshooting (Uc400) - Trane HUV Installation, Operation And Maintenance Manual

Horizontal unit ventilator
Table of Contents

Advertisement

two seconds.The green LED will begin to blink, indicating
the controller is in test mode.
Table 47.
Test sequence for 1-heat/1-cool configurations
(Tracer ZN520)
Fan
Steps
BOP1-3
1. Off
Off
2. Fan High
High
3. Fan Medium
Medium
4. Fan Low
Low
5. Cool
High
6. Heat
High
(b)
7. Fresh Air Damper
High
(c)
8. Exit
Note: For all 1-heat/1-cool applications including 2-pipe changeover, BOP4
energizes in the cooling test stage and BOP5 energizes in the heat
test stage.This occurs even though during normal 2-pipe changeover
operation BOP4 controls the unit valve for both cooling and heating.
(a) At the beginning of the Fan High step, the controller attempts to clear
all diagnostics.
(b) The fresh air damper (BOP6) only energizes during this step if binary
output 6 has been configured as a fresh air damper.
(c) After the Fresh Air Damper step, the test sequence performs the Exit
step.This initiates a reset and attempts to return the controller to normal
operation.
UV-SVN02C-EN
Cool
Heat
Output
Output
Damper
(a)
BOP4
BOP5
BOP6
Off
Off
Closed
Off
Off
Closed
Off
Off
Closed
Off
Off
Closed
On
Off
Closed
Off
On
Closed
Off
Off
Open

Troubleshooting (UC400)

Table 48
through
Table 53, p. 103
information if encountering operational problems with the
UC400 controller.
Table 48. Fan does not energize (UC400)
Probable
Cause
Explanation
Unit wiring
The wiring between the controller outputs and the fan
relays and contacts must be present and correct for normal
fan operation. Refer to applicable wiring diagram.
Failed end
The fan motor and relay must be checked to ensure proper
device
operation.
Normal
The fan will turn OFF when:
operation
• The controller receives a communicated off signal
• The fan-speed switch is set to OFF if no communicated
value is present
• Specific diagnostics are generated
• The default fan speed is set to OFF and the fan is
operating in the Auto mode.
If the controller is in unoccupied mode, the fan cycles
between OFF and the highest fan speed.
No power to
If the controller does not have power, the unit fan does not
the controller
operate. For the controller to operate normally, it must
have an input voltage of 24 Vac. If the Marquee/Power LED
is OFF continuously, the controller does not have sufficient
power or has failed.
Diagnostic
Several diagnostics affect fan operation. For detailed
present
information about these diagnostics, refer to
p.
93.
Unit
The controller must be properly configured based on the
configuration
actual installed end devices and application. If the unit
configuration does not match the actual end device, the
fans may not work correctly.
Random start
After power-up, the controller always observes a random
observed
start from 5 to 30 seconds. The controller remains OFF
until the random start time expires.
Cycling fan
The controller continuously operates the fan when in the
operation/
occupied, occupied standby, or occupied bypass mode.
continuous
When the controller is in the unoccupied mode, the fan is
cycled between high speed and OFF with capacity.
Unoccupied
Even if the controller is configured for continuous fan
operation
operation, the fan normally cycles with capacity during
unoccupied mode. While unoccupied, the fan cycles ON or
OFF with heating/cooling to provide varying amounts of
heating or cooling to the space.
Fan mode off
If a local fan mode switch determines the fan operation, the
OFF position controls the fan to off.
Requested
The user can communicate a desired operating mode (such
mode off
as OFF, heat, and cool) to the controller. If OFF is
communicated to the controller, the unit controls the fan to
off. There is no heating or cooling.
Table 49. Valves remain closed (UC400)
Probable
Cause
Explanation
Unit wiring
The wiring between the controller outputs and the valve(s)
must be present and correct for normal valve operation.
Refer to applicable wiring diagram.
Failed end
The valves must be checked to ensure proper operation.
device
No power to
If the controller does not have power, the unit valve(s) will
the controller
not operate. For the controller to operate normally, apply
an input voltage of 24 Vac. If the Marquee/Power LED is
OFF continuously, the controller does not have sufficient
power or has failed.
Diagnostic
Several diagnostics affect valve operation. For detailed
present
information about these diagnostics, refer to
p.
93.
Normal
The controller opens and closes the valves to meet the unit
operation
capacity requirements.
Diagnostics
provide troubleshooting
Table 37,
Table 37,
101

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Huvc

Table of Contents