ELECTRICAL INSTALLATION

UNITS WITH 6CN and 6CLP CONTROLS

The control system on this fireplace is powered by the thermocouple and operates on approximately
500m V (one-half volt). All connections in the wiring must be clean and tight. The wall switch should be
located as near the fireplace as practical. Do not locate the wall switch so that more than 25' of wire
provided must be used. Additional wire and splices will cause a voltage drop and may cause the control
system to not operate.
1. Determine a conventional location within 20' and cut a hole large enough to accommodate the wall
switch yet be covered with a wall plate. It is not necessary to use a wall box, but one may be used.
2. Route the wire provided through the 1/2" black plastic grommet in the unit.
3. Route the wire into the wall box, connect it to the switch, mount the switch and cover.
4. Set the wall switch to "OFF".
5. Light the pilot according to instructions.
To Thermocouple
Generator
Manifold Tubing
Pilot Tubing
Tp Thermocouple
Figure 18
53D9009
Limit Switch
Wall Switch
To Piezo Electrode
SIT 820 NOVA Control
FP2212
6CN CLP wiring
B-Vent Specialty Gas Fireplaces
OFF/PILOT/ON Control Knob
Inlet Pressure Tap
19