E. Vent Diagrams
Fire Risk. Explosion Risk.
Do NOT pack insulation or other combustibles between ceiling fi restops.
• ALWAYS maintain specifi ed clearances around venting and fi restop systems.
• Install wall shield and ceiling fi restops as specifi ed.
Failure to keep insulation or other material away from vent pipe may cause fi re.
Top Vent - Horizontal Termination
Venting with 1 elbow
V Minimum
SL-550TR-E
90 Elbow
2 ft.
610 mm
1/2 ft.
152 mm
2 ft.
610 mm
1-1/2 ft. 457 mm
3 ft.
914 mm
2-1/2 ft. 762 mm
5 ft.
1.5 m
3-1/2 ft.
1.1 m
7 ft.
2.1 m
4-1/2 ft.
1.4 m
15 ft.
4.6 m
H MAX. =15 FT (4.6 m)
V + H MAX. = 40 FT (12.2 m)
Fire Risk.
• When using SL-HRC-SS and SL-HRC-ZC-SS
termination caps on top vented fi replaces, a one
foot minimum vertical vent section is required
before installing fi rst elbow.
Figure 5.4
H
Maximum
1
SL-750TR-E
SL-950TR-E
2 ft.
610 mm
1 ft.
305 mm
2 ft.
610 mm
2 ft.
610 mm
3 ft.
914 mm
3 ft.
914 mm
5 ft.
1.5 m
5 ft.
1.5 m
7 ft.
2.1 m
7 ft.
2.1 m
15 ft.
4.6 m
15 ft.
4.6 m
H
1
WARNING
Heat & Glo • SL-550 / 750 / 950TR-E • 2118-900 Rev. D • 6/07
WARNING
Note: Use SL D- Series
components only.
Note: There MUST be a 25%
reduction in total H when using
fl ex vent except when using the
simple up and out installation
(see Figure 5.3).
V
1
15