Schwank STS-JZ Installation & Owner's Manual page 32

Low intensity tube type infra red heaters
Table of Contents

Advertisement

V
ERTICAL VENT THROUGH THE ROOF
It is the sole responsibility of the installer to
adhere to all current local codes and/or ANSI
Z223.1 / CSA.B149.1 latest editions for all
venting requirements, and practices.

Use an approved 'B-vent' termination cap
as supplied by the manufacturer of the ap-
proved 'B-vent'.

When vent and combustion air are taken
through the roof, the exhaust vent should
always terminate higher than the combus-
tion air intake, to prevent recycling the
products of combustion back into the
heater

At most a quantity of three 90° elbows can be installed in a vertical vent
11A. Combined System Length: Tube Heater + Vent + Combustion Air Duct
MINIMUM VENT LENGTH: (Vented or Unvented)

Minimum vent length of 3 ft (91 cm) is required
MAXIMUM SYSTEM LENGTH (includes: Tube Heater length + combustion air duct + vent):

Each 90° elbow in the system has an equivalent length of 5 ft.

A maximum of 2 elbows are allowed in any portion (duct, tube heater, vent) with the ex-
ception of up to three 90° elbows in a vertical vent run through the roof

The maximum length of combustion air duct to any heater is not to exceed 30 feet

Exceeding the allowable lengths in the table below can create combustion and/or conden-
sation problems and will void CSA Design Certification and the heater warranty.
Max. Combined
Input
System Length*
(Btuh)
Do Not Exceed
45,000
60,000
80,000
100,000
110,000
130,000
155,000
175,000
200,000
* Do not exceed the Maximum Combined System Length regardless of the allowed maximum
length of individual vent or combustion air duct
STS-JZ / IQ I&O Manual
IM101220
RD: MAY 2012
RL: 14D - BA
:
Max. Vent
Length*
60 ft
Up to 30 ft
60 ft
Up to 30 ft
80 ft
Up to 40 ft
Up to 30 ft
60 ft
100 ft
Up to 40 ft
100 ft
Up to 40 ft
100 ft
Up to 40 ft
120 ft
Up to 50 ft
120 ft
Up to 50 ft
FIGURE 22
Approved
Cap
Approved
'B' Vent
Max. Air Duct
Length*
Up to 20 ft
Example
Up to 30 ft
155,000 Btuh Heater:
Up to 30 ft
Tube Heater Length
Up to 30 ft
1 x 90° elbow (vent)
Up to 30 ft
Straight vent
Up to 30 ft
1 x 90° elbow (duct)
Up to 30 ft
Air Duct
Combined Length
Up to 30 ft
Max. Allowed
Up to 30 ft
32
24"
60 cm
9
Up
to
12
If roof slope exceeds 9:12
consult NFPA-54 ANSI
Z223.1 or CSA-B149.1
100 ft
:
50 ft
5 ft
20 ft
5 ft
17 ft
97 ft