Scheduled operation using the UPS monitoring software
● When performing scheduled operation in which the UPS is stopped and a device such as a breaker is
used to stop the UPS at the same time that commercial power stops, specify a period of no more than
3 months for the start of the next operation.
If you specify a period longer than 3 months, the internal timer is reset and the scheduled operation
does not start.
Note that this period reduces to approximately half when the battery is dead.
If a period of 3 months is exceeded, you start operation by supplying commercial power and pressing
the Start Switch. However, if the battery is dead, you may not be able to start operation. In this case,
replace the battery according to "6-2 Replacing the battery" on page 32.
Start of operation in scheduled operation using the UPS monitoring software
● To manually start up this unit after it has been stopped by a scheduled operation, turn OFF the power
switch and turn it back ON again.
To stop the unit when it is in operation, turn OFF the power switch.
Auto restart after OS closing processing using the UPS monitoring software
● When a power failure occurs, certain PCs (*1) automatically restart immediately after the OS is shut
down by auto shutdown.
In this case, the UPS stops during or after the restart of the PC, which may damage fi les and the hard
disk. You can avoid this phenomenon by disabling POWER MANAGEMENT in the BIOS settings of the
PC.
*1) Certain PC: It is known that this phenomenon occurs for MICRON's Millennia Mme.
When performing auto-save functions using the
7-2
UPS service in Windows Server 2003/XP/2000 +
UPS service driver
When using the included "UPS service driver", the OS standard UPS service in Windows Server 2003/
XP/2000 can be used. When there is a power failure, fi les can automatically be saved and the computer can
be shut down.
1. Connect the UPS to a computer.
Cable: Included connection cable (RS-232C)
2. Install the included "UPS service driver" on the computer.
Software to install: UPS service driver
How to install: Refer to the separate "UPS monitoring software installation guide".
Explanation
Connect to
RS-232C
terminal
Connector
Connect to RS-232C
port on PC
Included connection cable
50
75
BU
SW / BU
SW / BU
Connector
Connect to
RS-232C
connector on UPS
100
150
SW / BU
SW
1
2
3
4
5
6
7
8
9
1 0