Cooling Setpoint Limit
Press the
NEXT
key to select
set the minimum allowable cooling setpoint.
The minimum cooling setpoint range is 55 to 80F.
10

Programming the Module

If there is only one WZ-1 installed, it is not necessary to program the address as the thermostat and damper
control module default address is Zone 01.
After selecting the Zone number for the thermostat, the same address must be programmed into the damper control
module. Remove the cover on the module and apply 24 Volts power. Press the
module will accept a new address for thirty seconds. The LED on the module will alternately blink red and green while it is
waiting for a new address. When the module accepts the address, the LED will begin to flash green confirming
communications with the thermostat.
The multi-colored LED indicator normally flashes green when no calls are active. The LED is continuously
yellow during cooling calls and red during heating calls.
While the module LED is alternately blinking red and green, press and hold
the
ENTER
key for seven second until the zone number is displayed. Press
NEXT
until
Option 03 (Pr)
zone address to the damper control module by pressing the
When the module LED begins to flash green, communications with the
thermostat has be enabled.
Option 09
and press the
24 VAC
FLASHING LED
LED
G Y W R C
and the zone number are displayed. Send the
Up
or
Down
key to
ACTUATOR
PO / SC
PROGRAM
ENABLE
BUTTON
GREEN
LED
1
2 3 4
5 6
7
ENTER
key.
5
Option
CANCEL
PROGRAM ENABLE
ON WHEN DAMPER
IS POWERED OPEN
Option
CANCEL
Cool
Set To
NEXT
ENTER
button. The
Zone
NEXT
ENTER

Advertisement