2.1 Technical specifications

Maximum operating pressure: 6 bar
Boiler thermostat setting: 30 to 90°C
Boiler
Useful output
Power input
Number of sections
Water content
Water resistance
∆ T = 15K
Pressure in the furnace for
nozzle pressure = 0
(1) (3)
Flue gas temperature
Fuel oil
(1)
Mass flue gas flow rate
Gas
Inscribed diameter
Depth
Combustion chamber
Volume
Maintenance consumption
by 50°C
Shipping weight
(1)
Nominal operation (top boiler power)
(2)
CO
= 13.1 to 13% with fuel oil and 9.5% with natural gas
2
(3)
Boiler temperature: 80 °C, Ambient temperature: 20 °C
1 mbar = 10 mmWG = 10 daPa
In order for the boiler to operate correctly, it is imperative
to respect the draught at the nozzle: 0 at the nozzle.
6
P 320-4
kW
70-105
kW
76-117
4
l
96
(1)
mbar
6.2
mbar
+0.3
°C
< 210
Kg/h
178
Kg/h
187
mm
377
mm
621
3
0.096
m
%
0.17
kg
610
.
Safety thermostat setting: 110 °C
P 320-5
P 320-6
105-140
140-180
115-156
153-199
5
6
116
136
10.9
20.4
+0.6
+1.1
< 210
< 210
238
306
250
321
377
377
781
941
0.122
0.148
0.14
0.13
739
845
P 320
P 320-7
P 320-8
180-230
230-280
197-253
252-309
7
8
156
176
30
44.5
+1.6
+2.2
< 210
< 210
391
475
410
499
377
377
1101
1261
0.174
0.200
0.11
0.10
980
1101
20/09/2011 - 300016243-001-D
P 320-9
280-330
305-361
9
196
63.8
+2.5
< 210
560
588
377
1369
0.226
0.09
1228