1. Fireplace Locations and Space Requirements
Several options are available to you when choosing a location for your fireplace. This fireplace may be used as a
room divider, installed along a wall, across a corner or used in an exterior chase. See Figure 2.
Locating the fireplace in a basement, near frequently opened doors, central heat outlets or returns, or other locations
of considerable air movement can affect the performance and cause intermittent smoke spillage from the front of
the fireplace. Consideration should be given to these factors before deciding on a location.
Figures 3 and 4 show two typical installations assuming an outside air kit is being used. Therefore, an allowance must
be made for 90-deg bends. Less space is required when ducting goes directly outside without forming elbows.
Installation Along a Wall or an Exterior Chase
Do not draw outside air from garage spaces. Exhaust products of gasoline engines are hazardous.
Do not install outside air ducts such that the air may be drawn from attic spaces, basements or above the
roofing where other heating appliances or fans and chimneys exhaust or utilize air. These precautions will
reduce the possibility of fireplace smoking or air flow reversal.
To prevent contact with sagging or loose insulation, the fireplace must not be installed against vapor barriers
or exposed insulation. Localized overheating could occur and a fire could result.
10
D. PRE-INSTALLATION PREPARATION
Figure 2 - Fireplace Locations
Cat #
A
B
42 in
45 in.
E/EC36
1067 mm
1143 mm
45 in.
48 in.
E/EC39
1143 mm
1219 mm
48 in.
51 in.
E/EC42
1219 mm
1295 mm
Figure 3
E36/39/42 INSTALLATION INSTRUCTIONS
These are
rough
framing
dimensions
only.
Cat #
E/EC36
E/EC39
E/EC42
WARNING!
WARNING!
17335 Rev L
CLEARANCES!
A
minimum
clearance
maintained at the back and
sides
of
assembly.
Chimney sections at any level
require a 2 in. minimum air
space clearance between the
framing and chimney section.
A
B
C
42 in.
72-3/4 in.
36-3/8 in.
1067 mm
1848 mm
924 mm
45 in.
75-3/4 in.
37-7/8 in.
1143mm
1924 mm
962 mm
48 in.
78-3/4 in.
39-3/8 in.
1219 mm
2000 mm
1000 mm
Figure 4
Corner Installation
1/2 in.
air
must
be
the
fireplace
D
E
15-5/8 in.
51-3/8 in.
397 mm
1305 mm
16-5/8 in.
53-1/2 in.
422 mm
1359 mm
17-5/8 in.
55-3/8 in.
448 mm
1407 mm