delta Service Software

The Delta Service Software enables the installer to adapt settings, realize firmware
upgrades and other updates besides supporting him in detecting error sources, like e.
g. over- or undervoltage -without any need to open the inverter. The memory from every
inverter can be stored and readout with the software in order to facilitate maintenance
and on-site service. Detailed information of every inverter can be monitored and if nec-
essary adapted.
The SOLIVIA gateway replaces the service software kit, that consists out of a Delta
RS485 special cable and a USB to RS485 converter. Therefore, beside the gateway
and the software itself, which can be downloaded from our website free of charge, no
further equipment nor tools are necessary.
Proceed as follows:
1.
Connect a RS485 cable between the RS485 connector on the SOLIVIA gateway
and the RS485 connector on the SOLIVIA inverter.
2.
Connect an Ethernet network cable between the SOLIVIA gateway and the
internet ready network port.
3.
Donwload the software from our website free of charge.
4.
Start the service software program.
NOTICE
Please make sure, that your internet connection is active!
For further information about the SOLIVIA service software, please refer to our website
at www.solar-inverter.com.
12

reset Button

The reset button offers two different functionalities. Please also refer to Chapter 10 for
further information on the below mentioned configuration parameters.
1.
Keep the reset button pressed > 5 seconds and < 20 seconds
LED blinks very fast for one second to indicate the reset has been recognized.
»
Does a soft reset of the configuration parameters.
»
Baud rate, interval time, power management, and unbalanced settings are not
»
changed (except that "use unbalanced" is switched off). The other parameters
are reset to default:
DHCP active
ü
Proxy not active
ü
Wireless RS485 modem not active
ü
Unbalanced correction not active
ü
Default IPs in subnet 192.168.0.200
ü
Proxy IP 0.0.0.0
ü
Default password (000000) and username (Delta)
ü
Inverter list is cleared
»
22