To dismount, pull the gateway's DIN rail latch OUT. Then, tilt the bottom part of the unit
out, push the unit up and pull out from the DIN rail.
7.2.2

Mounting directly to the Wall

Mount the gateway with appropriate screws to the wall
Use the 2 screws specified in Chapter 5.1 to mount the gateway with the DIN Rail to the
wall. Center-to-center distance between the two boreholes is 70 mm.
Figure 2: Mounting the gateway directly to the wall
7.3

rS485 Connection

Connect a standard CAT cable between the RS485 connector on the SOLIVIA gateway
and the RS485 connector on the SOLIVIA solar inverter. See step 1 in figure 4 below.
7.4

Ethernet Connection

Connect an Ethernet network cable between the SOLIVIA gateway and the internet
connected network point. See step 2 in figure 4.
7.5

Connection of the ripple Control receivers

You are able to connect the digital inputs to a given function. This concerns the control
of the power the inverter feeds to the grid (power management) and of the power factor
(reactive power control).
If your local public grid supplier requires a remote power derating capability, this can
be implemented by using a ripple control receiver. Please connect the ripple con-
trol receiver as shown in figure 3. After the configuration as shown in Chapters 10.5
and 10.6 the public grid supplier is capable to remotely limit the maximum power the
SOLIVIA solar inverters provide to the public grid.
Operation and installation manual SOLIVIA Gateway M1 G2
70 mm
EN
9