10.5.1

Power Management

There are four binary inputs that control the maximum power the inverter may feed into
the grid.
Power management is at 100 % for all relay state combination except 60 % for relay 1,
30 % for relay 2, and 0 % for relay 3 (default settings).
10.5.2

Power Factor Control

The power factor configuration page allows the definition of 15 values for the cos φ,
either inductive or capacitive. If all inputs are inactive the cos φ is 1.00.
The values are entered in the form 0.xx, e.g. 0.95 and a checkbox decides whether it is
leading current (capacitive) or not.
NOTICE
Please remember to save the configurations by pressing the "Submit" button.
1) This chapter is only relevant for countries, in which your public grid supplier requires a power reduction
(power management), power factor control and/or power balancing.
18