24. TROUBLESHOOTING GUIDE — HEATER OPERATION — FENWAL DSI
WARNING
SEQUENCE OF EVENTS (also see DSI Troubleshooting previous page)
APPLY 120 VOLTS - GREEN LIGHT
SET THERMOSTAT TO CALL FOR
COMBUSTION AIR BLOWER
YES
AIR PROVING SWITCH HAS
CLOSED 24 VOLTS IS PRESENT
AT "PSW" AT DSI CONTROL.
YES
BLOCKED FLUE SWITCH IS
CLOSED
24 VOLTS IS PRESENT AT "TH" AT
YES
SPARK IGNITER / SENSOR
YES
24V TO GAS VALVE - RED LIGHT
CONTINUED
Improper adjustment, alteration, service or maintenance can
cause property damage, injury or death. This heater must be
installed and serviced only by a trained gas service technician
NO
REMEDY 120 VOLTS SUPPLY FAULT
CHECK 120V TO DSI AT "L1"
NO
CHECK 120V OUT AT "IND" FROM DSI TO
NO
FAULTY RELAY SWITCH IN DSI — RE-
PLACE DSI
CHECK TUBING TO SWITCH IS CON-
NO
NECTED AND NOT BLOCKED OR KINKED
CHECK AIR PRESSURE WITH MANOME-
TER
CHECK FOR OBSTRUCTION IN THE AIR
INTAKE
CHECK TUBING TO SWITCH IS CON-
NO
NECTED AND NOT BLOCKED OR KINKED
CHECK AIR PRESSURE WITH MANOME-
TER
CHECK INTEGRITY OF SWITCH
NO
CHECK DSI CONTROL FUSE FOR CONTI-
NUITY
VISIBLY CHECK IF IGNITER IS SHORTING
OUT
CHECK GROUND WIRING
REMOVE AND INSPECT IGNITER AND
LEAD
CHECK BOOT OF THE IGNITION CABLE
FOR SIGNS OF MELTING OR OVERHEAT-
ING
IF "YES" ... TAKE PROTECTIVE ACTION TO
SHIELD CABLE AND BOOT FROM EXCES-
SIVE TEMPERATURE; REPLACE ANY DE-
FECTIVE COMPONENT