Model CSV Vertical R-410A Air Conditioning Units Supersedes: 145.15-IOM7 (312) Form 145.15-IOM7 (412) MODEL CSV060B-240B VERTICAL R-410A WATER COOLED AIR CONDITIONING UNITS INSTALLATION INSTRUCTIONS B Style...
All wiring must be in accordance with published specifications and must be performed ONLY by qualified service personnel. Johnson Controls will not be responsible for damages/problems resulting from improper connections to the controls or application of improper control signals.
FORM 145.15-IOM7 (412) CHANGEABILITY OF THIS DOCUMENT In complying with Johnson Controls policy for continu- It is the responsibility of operating/service personnel as ous product improvement, the information contained in to the applicability of these documents to the this document is subject to change without notice.
INDIVIDUAL UNIT WEIGHTS (PAGE 10) CSV096B AND VERIFY LIFTING CAPACITY OF LIFTING EQUIPMENT EXCEEDS WEIGHT CSV120B OF UNITS BY SAFE MARGINS. FAILURE CSV180B 1310 1365 TO DO SO MAY RESULT IN UNIT CSV240B 1465 1525 DAMAGE, PERSONAL INJURY OR EVEN DEATH. JOHNSON CONTROLS...
- Install the securing brackets at all four corners, on the evaporator/condenser separation joint. Note that one bracket, intended for use at the corner with the +drain fitting, has a short "leg". JOHNSON CONTROLS...
Secure the wiring so that it does alternate location access panel (front blower not contact the evaporator coil. module panel). The front roof support angle must be removed to allow access to the front panel. Remove the panel and set aside. JOHNSON CONTROLS...
JURY OR DEATH DUE TO ELECTRICAL 125 feet require 16 gauge wire. SHOCK. All models are designed for single zone cooling applications, utilizing space or return air thermostatic controls. A low voltage terminal block is provided for hook-up conventional programmable thermostats. JOHNSON CONTROLS...
4) Once the pulley has been opened/closed the appropriate number of turns, replace the external key and tighten the adjustment setscrew. Proper torque is 110-130 in.-lbs. 5) Install drive belt and adjust motor mount to tension belt. LD13547 BELT TENSION ADJUSTMENT DEFLECTION FORCE VERSUS DRIVE BELT CROSS-SECTION JOHNSON CONTROLS...
30 seconds. Additionally, the indoor blower compressor, initiate the ASCD, and stop the fan. has a delay of 10 seconds between operations. Once the low-pressure switch has been proven (closed during the 30-second monitoring period as JOHNSON CONTROLS...
In addition to the external pressure switches, the compressor also has inherent (internal) protection. If there abnormal temperature rise compressor, the internal protection will immediately shut down the compressor. The microprocessor control incorporates features to minimize compressor wear and damage. An anti-short cycle delay (ASCD) JOHNSON CONTROLS...
Page 25
Compressor(s) locked out due to Economizer running (Free Cooling) * 13 Flashes Compressor Held Off due to Low Voltage 14 Flashes EEPROM Storage Failure No Power or Control Failure Note: Flash rates marked with * are NOT alarms. JOHNSON CONTROLS...
(movement between inner and outer races). Ensure bearing locking collars are secure to the shaft, and that collar locking screw is properly set. Check that the blower wheel is tight on the shaft, and that the hub screws properly torqued. JOHNSON CONTROLS...
Do not use an R-22 TXV. If a TXV is to be used, it must be an R-410A TXV. • Never open system to atmosphere when under vacuum. • If system must be opened for service, evacuate system then break the vacuum with dry nitrogen and replace filter driers. JOHNSON CONTROLS...