R-410a 2-stage outdoor split-system air conditioning

Advertisement

Quick Links

INSTALLATION MANUAL
R-410A 2-STAGE OUTDOOR
SPLIT-SYSTEM AIR CONDITIONING
MODELS: 17 & 19 SEER
YFK, CC17, TC17,
YXT, AC19, AL19 SERIES
2 - 5 TONS - 1 PHASE
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
SAFETY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
UNIT INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
COIL METERING DEVICES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
EVACUATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Typical Installation Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Alternative Installation Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Insulation of Vapor Line . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Underground Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Heat Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
TXV Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
TXV Bulb and Equalizer Line Installations . . . . . . . . . . . . . . . . . . . . . .7
Proper TXV Bulb Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Vertical Temperature Bulb Orientation . . . . . . . . . . . . . . . . . . . . . . . . .7
System Charging Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Outdoor Unit Control Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
Typical 2-Stage Conventional Field Wiring - AC . . . . . . . . . . . . . . . .11
Minimum / Maximum Operating Limit Conditions . . . . . . . . . . . . . . . . .2
R-410A Saturation Properties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Status Code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
IMPORTANT: It is recommended before starting the system to con-
nect the thermostat to Wi-Fi using a local network or portable hot-
spot so the thermostat and system receive the latest software
updates to optimize system performance only if using this in commu-
nicating configuration. This notice does not apply to conventionally
wired equipment.
SECTION I: GENERAL
The outdoor units are designed to be connected to a matching indoor
coil with sweat connect lines. Sweat connect units are factory charged
with refrigerant for a nominal sized matching indoor coil plus 15 feet of
field-supplied lines.
SECTION II: SAFETY
This is a safety alert symbol. When you see this symbol on
labels or in manuals, be alert to the potential for personal
injury.
Understand and pay particular attention to the signal words DANGER,
WARNING, or CAUTION.
DANGER indicates an imminently hazardous situation, which, if not
avoided, will result in death or serious injury.
WARNING indicates a potentially hazardous situation, which, if not
avoided, could result in death or serious injury.
CAUTION indicates a potentially hazardous situation, which, if not
avoided may result in minor or moderate injury. It is also used to
alert against unsafe practices and hazards involving only property dam-
age.
Johnson Controls Ducted Systems
LIST OF SECTIONS
SYSTEM CHARGE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
ELECTRICAL CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
INSTRUCTING THE OWNER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
WIRING DIAGRAMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
START UP SHEET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
LIST OF FIGURES
Conventional Low Voltage Molex Plug . . . . . . . . . . . . . . . . . . . . . . . 12
Demand Response Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
17 SEER 2-Stage Equipment - Wiring Diagram . . . . . . . . . . . . . . . . 24
19 SEER 2-Stage Equipment - Wiring Diagram . . . . . . . . . . . . . . . . 25
LIST OF TABLES
Status Code Display & Timing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Fault Code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Improper installation may create a condition where the operation of
the product could cause personal injury or property damage.
Improper installation, adjustment, alteration, service or maintenance
can cause injury or property damage. Refer to this manual for assis-
tance or for additional information, consult a qualified contractor,
installer or service agency.
This product must be installed in strict compliance with the enclosed
installation instructions and any applicable local, state, and national
codes including, but not limited to building, electrical, and mechanical
codes.
R-410A systems operate at higher pressures than R-22 systems. Do
not use R-22 service equipment or components on R-410A equip-
ment. Service equipment
®
WARNING
!
CAUTION
!
CAUTION
!
Must Be Rated
for R-410A.
5512532-UIM-D-0320

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the YFK Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Johnson Controls YFK Series

  • Page 1: Table Of Contents

    CAUTION indicates a potentially hazardous situation, which, if not avoided may result in minor or moderate injury. It is also used to alert against unsafe practices and hazards involving only property dam- age. Johnson Controls Ducted Systems 5512532-UIM-D-0320...
  • Page 2: Unit Installation

    35 deg F. If run in cooling, mode below Below Provide adequate structural support for the unit. 35 Deg F the unit will lockout. Refer to www.simplygettingthejobdone.com or price pages for the appropriate Crank Case Heater for your model. Johnson Controls Ducted Systems...
  • Page 3: Typical Installation Clearances

    5512532-UIM-D-0320 FIGURE 1: Typical Installation Clearances FIGURE 2: Alternative Installation Clearances Johnson Controls Ducted Systems...
  • Page 4 Wall mounting requires 3 ity must also be insulated. mounting brackets and best served by a properly engineered solution. See price pages for specific part number for your application. Johnson Controls Ducted Systems...
  • Page 5: Insulation Of Vapor Line

    Go to SECTION IV for TXV installation. Leak test all refrigerant piping connections including the service port flare caps to be sure they are leak tight. DO NOT OVER- TIGHTEN (between 40 and 60 inch - lbs. maximum). Johnson Controls Ducted Systems...
  • Page 6: Coil Metering Devices

    1/3 turn to seal. See Figure 7. cedure is followed. CAUTION In all cases, mount the TXV temperature sensing bulb after vapor line is brazed and sufficiently cooled. Failure to use suction line split grommet may result in TXV failure. Johnson Controls Ducted Systems...
  • Page 7: Evacuation

    (i.e. -.10) return, add it to a supply static (.40) which equals a (.50) total system static pressure. Compare this value to the table for the indoor unit's static pressure vs. CFM or to a curve chart. Johnson Controls Ducted Systems...
  • Page 8 IT IS UNLAWFUL TO KNOWINGLY VENT, RELEASE OR DIS- CHARGE REFRIGERANT INTO THE OPEN AIR DURING REPAIR, SERVICE, MAINTENANCE OR THE FINAL DISPOSAL OF THIS UNIT. Johnson Controls Ducted Systems...
  • Page 9: System Charging Connections

    POE oil in the system. the matched coil and follow guidelines in this instruction. This type of oil is highly susceptible to moisture absorption. Johnson Controls Ducted Systems...
  • Page 10: Outdoor Unit Control Box

    Before measuring the pressures, use the method above to check the air flow and then consult the table and match the liquid pressure to that air FIGURE 11: Outdoor Unit Control Box flow. Johnson Controls Ducted Systems...
  • Page 11: Typical 2-Stage Conventional Field Wiring - Ac

    5512532-UIM-D-0320 FIGURE 12: Typical 2-Stage Conventional Field Wiring - AC FIGURE 13: Typical Communicating Field Wiring (Air Handler / Furnace) Johnson Controls Ducted Systems...
  • Page 12: Conventional Low Voltage Molex Plug

    Do not place it on an outside wall or where it is exposed to the radiant effects from exposed glass, appliances, drafts from outside doors, or supply vents. A1072-001 FIGURE 15: Communicating Low Voltage Molex Plug (19 SEER) Johnson Controls Ducted Systems...
  • Page 13: Demand Response Wiring

    Manually setting the airflow on the Indoor Control is required with the Hx™ communicating thermostat. Set the cooling speed per the instructions defined in the air handler or furnace. Verify the airflow, after the configuration has be set on the Indoor Control. Johnson Controls Ducted Systems...
  • Page 14: Thermostat Chart - Two Stage Ac - Two Stage Furnace

    5512532-UIM-D-0320 THERMOSTAT CHARTS FIGURE 18: Thermostat Chart - Two Stage AC – Two Stage Furnace Johnson Controls Ducted Systems...
  • Page 15: Thermostat Chart - Two Stage Ac - Two Stage Furnace

    5512532-UIM-D-0320 FIGURE 19: Thermostat Chart - Two Stage AC – Two Stage Furnace Johnson Controls Ducted Systems...
  • Page 16: Thermostat Chart - Two Stage Ac - Modulating Furnace

    5512532-UIM-D-0320 FIGURE 20: Thermostat Chart - Two Stage AC – Modulating Furnace Johnson Controls Ducted Systems...
  • Page 17: Thermostat Chart - Two Stage Ac - Modulating Furnace

    5512532-UIM-D-0320 FIGURE 21: Thermostat Chart - Two Stage AC – Modulating Furnace Johnson Controls Ducted Systems...
  • Page 18: Thermostat Chart - Two Stage Ac - Variable Speed Air Handler

    “YES” if humidistat is to be used. Refer to AH documentation for W1 and W2 electric heat staging options. Part Number: S1-2HU16700124 A0924-002 FIGURE 22: Thermostat Chart - Two Stage AC – Variable Speed Air Handler Johnson Controls Ducted Systems...
  • Page 19: Thermostat Chart - Two Stage Ac - Variable Speed Air Handler

    5512532-UIM-D-0320 FIGURE 23: Thermostat Chart - Two Stage AC – Variable Speed Air Handler Johnson Controls Ducted Systems...
  • Page 20: Status Code

    Control normal operation – call for first-stage cooling compressor Green Control normal operation – call for second-stage cooling compressor Green Demand Response Green No fault codes in memory 2 flashes Green – – Fault code memory cleared 3 flashes Green – – Johnson Controls Ducted Systems...
  • Page 21: Status Code Display & Timing

    Outdoor ambient sensor failure (open) Control senses an open sensor ODF will operate at (solid) units Max PWM. Control senses a shorted sensor 2 RED Discharge line sensor failure (short) Soft Lockout 1 fault occurrence flashes Johnson Controls Ducted Systems...
  • Page 22 2 RED Y2 present without Y1 Soft Lockout 1 fault occurrence flashes Configuration Error Jumpers Set to 00000 without a factory 2 RED Configuration Error configuration, no tonnage selected, or Soft Lockout flashes incorrect tonnage set. Johnson Controls Ducted Systems...
  • Page 23: Instructing The Owner

    Should an outdoor fan motor failure ever occur requiring replacement, the outdoor fan motor must be replaced with the original OEM part num- ber through Source 1. Refer to unit repair parts list to find the appropri- ate replacement part number. Johnson Controls Ducted Systems...
  • Page 24: Wiring Diagrams

    5512532-UIM-D-0320 SECTION IX: WIRING DIAGRAMS COMM COMM B- C B- C FIGURE 24: 17 SEER 2-Stage Equipment - Wiring Diagram Johnson Controls Ducted Systems...
  • Page 25: Seer 2-Stage Equipment - Wiring Diagram

    5512532-UIM-D-0320 COMM COMM B- C B- C FIGURE 25: 19 SEER 2-Stage Equipment - Wiring Diagram Johnson Controls Ducted Systems...
  • Page 26 5512532-UIM-D-0320 NOTES Johnson Controls Ducted Systems...
  • Page 27: Start Up Sheet

    Supply air wet bulb temperature Return static (inches of water column) Return air dry bulb temperature Return air wet bulb temperature Outside air dry bulb temperature Total external static pressure Temperature drop Page 1 of 2 (9/27/17) Johnson Controls Ducted Systems...
  • Page 28 Humid Comments and Additional Job Details Page 2 of 2 (9/27/17) Subject to change without notice. Published in U.S.A. 5512532-UIM-D-0320 Copyright © 2020 by Johnson Controls. All rights reserved. Supersedes: 5512532-UIM-C-0919 York International Corp. 5005 York Drive Norman, OK 73069...

This manual is also suitable for:

Cc17 seriesTc17 seriesYxt seriesAc19 seriesAl19 series

Table of Contents