System Power Specifications
Table B-4 and Table B-5 list the AC power requirements for an hp rp7405/rp7410 server. These tables provide
information to help determine the amount of AC power needed for your computer room.
Table B-4
AC Power Specifications
Requirements
Nominal input voltage
Minimum Operating Voltage
Maximum Operating Voltage
Frequency range (minimum -
maximum)
Number of phases
Rated line current
Maximum inrush current
Dropout carry-through time at
minimum line voltage
Circuit breaker rating
Branch Circuit Breaker (Size,
Type)
Power factor correction
Ground leakage current (mA)
kVA rating
Table B-5
System Power Requirements
Power Required (50 - 60 Hz)
Maximum configuration hp rp7405/rp7410 server PA8700
Typical configuration hp rp7405/rp7410 server PA8700
Future upgrades may increase the Maximum Theoretical System Power to 3400 VA.
Maximum power is the sum of the worst case power consumption of every subsystem in the box, and should
be used to size worst case power consumption for facility installation. Typical power consumption numbers
are what HP engineers have measured running power intensive applications. These are generally lower than
maximum power numbers due to the fact that getting all of the subsystems in the box to simultaneously draw
maximum power for long durations being uncommon.
96
Value
200, 208, 220, 240 VAC
180 VAC
269 VAC
50 - 60 (Hz)
1
12 A rms
30 A peak for 15 ms
20 ms
20 A
20A, slow trip delay
type
>0.97 @269VAC
>0.93 @262VAC
<3.0 (ma)
2.7 KVA
Comments
Per line cord
Per line cord
At all loads of 50% - 100% of
supply rating
At all loads 0f 30% - 50% of
supply rating
Per line cord
VA
Comments
3000
Theoretical
1700
Typical
Appendix B