Installation Instructions
Panic Keys
There are three Panic keys (A, B, and C) that, if programmed, can be used to manually initiate
alarms and send a report to the central station by pressing and holding the appropriate key for at
least 2 seconds. Each key can be programmed for 24-hour Silent, 24-hour Audible, Fire, or Personal
Emergency responses. The Panic keys are identified by the system as follows:
Keys
Displayed as Zone
[A] (∗/1)
[B] (∗/#)
[C] (3/#)

Various System Trouble Displays

Alpha Display
Fixed Disp. Meaning
ALARM CANCELED
CA
EXIT ALARM
EA
CHECK
CHECK
ALARM 1xx
1xx
FAULT 1xx
1xx
CHECK 1xx
1xx
91
SYSTEM LO BAT
BAT
LO BAT
BAT
Busy-Standby
dl
Modem Comm
CC
no display
no display
Comm. Failure
FC
Open Circuit
OC
Long Rng Trbl
bF
Bell Failure
70
RCVR Jam
90
KEYPAD LOW BAT
00 BAT
Phone Okay
Cd
Dialer Off
dO
Test in Progress
dd
Upload Completed
dC
Upload Failed
dF
6-6
IMPORTANT: For a Silent panic function (if programmed) to be of
95
practical value, you must program a report code for the zone and the
99
system must be connected to a central station.
96
will appear if an exit or interior zone contained a fault during closing at the time
the Exit Delay ended (e.g., exit door left open), but the system was disarmed during
the Entry Delay time. The alarm sounder and keypad sound continuously, but stop
when the system is disarmed. No message will be transmitted to the central station.
will appear when the Exit Delay ends if an exit or interior zone contained a fault
during closing. The alarm sounder and keypad sound continuously until the system
is disarmed (or timeout occurs). An "Exit Alarm" message is sent to the central
station.
Also results if an alarm from an exit or interior zone occurs within 2 minutes after
the end of an Exit Delay.
indicates that a problem exists with the displayed zone(s) and requires attention.
indicates that communication between control and a zone expander or wireless
receiver is interrupted, where "xx" is the device address. Check the wiring and
DIP switch settings on the units.
If field *199 is set to "1," all ECP module problems are displayed as "91."
If there are wireless sensors in the system, the Check condition may also be caused
by some change in the environment that prevents the receiver from receiving
signals from a particular sensor.
with no zone number indicates that the system's main standby battery is weak.
with a zone number and a once-per-minute beeping at the keypad indicates that a
low-battery condition exists in the wireless sensor displayed (zone "00" indicates a
wireless keypad). If the battery is not replaced within 30 days, a "CHECK" display
may occur.
NOTE: Some wireless sensors use a non-replaceable long-life battery which requires
replacement of the entire unit at the end of battery life (e.g., 5802, 5802CP).
If this remains displayed for more than 1 minute, the system is disabled.
The system is in communication with the central station for change of function or
status verification.
Power Failure
If there is no keypad display at all and the LEDs are unlit, operating power (AC and
battery) for the system has stopped and the system is inoperative.
If the message "AC LOSS" (Alpha display keypads) or "NO AC" (Fixed-Word display
keypads) is displayed, the keypad is operating on battery power only.
If the battery standby capacity is used up during a prolonged AC power outage, the
control's power will shut down to minimize deep discharge of the battery.
A communication failure has occurred.
The keypad is not receiving signals from the control and sees an open circuit.
Backup LRR communication failure.
Bell supervision failure.
RF jam detected.
Wireless keypad low battery
The dialer test has been successful (CID code 601).
The dialer is disabled.
Walk test mode is active(CID code 607).
The upload or download session was completed.
The upload or download session failed before completion.