Various System Trouble Displays - Honeywell VISTA 15P - Ademco 6 Zone Control Panel Installation And Operation Manual

Ademco vista series
Hide thumbs Also See for VISTA 15P - Ademco 6 Zone Control Panel:
Table of Contents

Advertisement

Installation and Setup Guide

Various System Trouble Displays

Alpha Display
Fixed Disp.
ALARM CANCELED
CA
EXIT ALARM
EA
CHECK
CHECK
ALARM 1xx
1xx
FAULT 1xx
1xx
CHECK 1xx
1xx
91
SYSTEM LO BAT
BAT
LO BAT
BAT
TELCO FAULT
94
Busy-Standby
dl
Modem Comm
CC
no display
no display
Comm. Failure
FC
Open Circuit
0C
Long Rng Trbl
bF
Bell Failure
70
RCVR Jam
90
KEYPAD LOW BAT
00 BAT
Phone Okay
Cd
Dialer Off
d0
Test in Progress
dd
Upload Completed
dC
Upload Failed
dF
3-8
Meaning
will appear if an exit or interior zone contained a fault during closing at the
time the Exit Delay ended (e.g., exit door left open), but the system was
disarmed during the Entry Delay time. The alarm sounder and keypad sound
continuously, but stop when the system is disarmed. No message will be
transmitted to the central station.
appears when Exit Delay ends if an exit or interior zone contained a fault
during closing. The alarm sounder and keypad sound continuously until the
system is disarmed (or timeout occurs). An "Exit Alarm" message is sent to the
central station. Also results if an alarm from an exit or interior zone occurs
within 2 minutes after the end of an Exit Delay.
indicates that a problem exists with the displayed zone(s) and requires
attention.
indicates that communication between control and a zone expander or wireless
receiver is interrupted, where "xx" is the device address. Check the wiring and
DIP switch settings on the units.
If field *199 is set to "1," all ECP module problems are displayed as "91."
If there are wireless sensors in the system, the Check condition may also be
caused by some change in the environment that prevents the receiver from
receiving signals from a particular sensor.
with no zone number indicates that the system's standby battery is weak.
with a zone number and a once-per-minute beeping at the keypad indicates
that a low-battery condition exists in the wireless sensor displayed (zone "00"
indicates a wireless keypad). If the battery is not replaced within 30 days, a
"CHECK" display may occur.
NOTE: Some wireless sensors contain a non-replaceable long-life battery which
requires replacement of the entire unit at the end of battery life (e.g., Nos.
5802, 5802CP).
Telephone Line Failure, indicates that a monitored telephone line (if
programmed in field *92) has been cut or disconnected. Depending on how the
system was programmed, the keypad may also produce a trouble sound, and
the external sounder may be activated. Silence by entering installer code +
OFF.
If this remains displayed for more than 1 minute, the system is disabled.
The system is in communication with the central station for change of function
or status verification.
Power Failure
If there is no keypad display at all and the LEDs are unlit, operating power
(AC and battery) for the system has stopped and the system is inoperative.
If the message "AC LOSS" (Alpha display keypads) or "NO AC" (Fixed-Word
display keypads) is displayed, the keypad is operating on battery power only.
If the battery standby capacity is used up during a prolonged AC power outage,
the control's power will shut down to minimize deep discharge of the battery.
A communication failure has occurred.
The keypad is not receiving signals from the control; sees an open circuit.
Backup LRR communication failure.
Bell supervision failure.
RF jam detected.
Wireless keypad low battery.
The dialer test has been successful (CID code 601).
The dialer is disabled.
Walk test mode is active(CID code 607).
The upload or download session was completed.
The upload or download session failed before completion.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents