Keypad Programming Fields

NOTE: Each keypad must be assigned a unique address. Keypads programmed with the same
address will give unpredictable results.
Address 16 is reserved for keypad 1, which is automatically set with all sounds enabled.
FIELD
TITLE and EXPLANATION
Keypad 2 Device Address 17
*190
Select whether or not this keypad is used, and enter the desired sound option for this keypad.
Keypad 3 Device Address 18
*191
Select whether or not this keypad is used, and enter the desired sound option for this keypad.
Keypad 4 Device Address 19
*192
Select whether or not this keypad is used, and enter the desired sound option for this keypad.
Keypad 5 Device Address 20
*193
Select whether or not this keypad is used, and enter the desired sound option for this keypad.
Keypad 6 Device Address 21
*194
Select whether or not this keypad is used, and enter the desired sound option for this keypad.
Keypad 7 Device Address 22
*195
Select whether or not this keypad is used, and enter the desired sound option for this keypad.
Keypad 8 Device Address 23
*196
Select whether or not this keypad is used, and enter the desired sound option for this keypad.
Exit Time Display Interval
*197
Select whether or not keypads display the exit time remaining after arming the system, with display
updates at the interval selected (i.e. if the exit delay is 30 seconds and "2" is selected in this field, the
keypad display refreshes every 2 seconds, displaying 30, 28, 26, 24, etc.).
An interval greater than "1" may be necessary for some older keypads to allow users time to enter key
presses between display updates.
FIXED-WORD KEYPAD NOTE: If using 2-digit display keypads (e.g. 6150RF), do not use exit times
greater than the 96-second delay option. Using a longer delay time may cause end-user confusion
because 2-digit display keypads cannot display times greater than "99." If longer exit time is required
by the installation, it is recommended that the Exit Time Display option be disabled ("0").
ECP Fail Display
*199
Select the 2-digit or 3-digit ECP Fail display, based on the type of keypads being used. The 3-digit
display option displays ECP faults as "1" plus the device address (00-30) of the device causing the fault
(e.g., faults on device 07 display as "107"), and is intended for Alpha keypads and/or 3-digit Fixed-Word
Display keypads.
The 2-digit Fixed-Word Display displays ECP faults for all devices as "91" on 2-digit displays, and
"191" on 3-digit or Alpha keypads. It is intended for 2-digit display keypads (e.g., certain 6128 series
keypads