Personalisation Using External Software - Eaton 700 Installation And User Manual

Pulsar series
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 1
Output personalisation
Function
Output voltage
Frequency converter
Output frequency
Transfer to the bypass
AC input
Overload level
(1) These parameters may be modified only when the UPS is OFF.
Detailed comments are available in the Personal Solution-Pac software.
ON/OFF personalisation
Fonction
Start on battery power
Automatic restart
Energy savings
Detection of phase/
neutral inversion (SWF)
Battery personalisation
Function
Battery test
Low-battery warning
Selection of the backup
time
Battery protection
against excessive
discharges

4.4 Personalisation using external software

Insert the Solution-Pac CD-ROM in the drive.
On the first navigation screen, select "Point to Point solution" and follow the instructions on how to install the
Personal Solution-Pac software.
Then select "Settings", "Advanced settings" and "UPS settings".
Note that the Linux/Unix/MacOS versions of the Personal Solution-Pac software do not offer this possibility.
4. Access to measurements and personalisation data
Factory setting
(1)
230 Volts AC
(1)
Disabled
(1)
Automatic selection
Bypass AC power must
(1)
be within tolerances
(1)
100%
Personnalisation usine
Enabled
Enabled
Disabled
Disabled
Factory setting
Weekly test
20%
Automatic detection of
number of battery
modules
Enabled
Other available settings
Comments
200/208/220/240/250 Volts
AC
Enabled
The connected devices are never
transferred to the bypass.
50 or 60 Hz
User selectable only if the
frequency-converter function is
enabled.
Bypass AC power may be
outside tolerances
30 / 50 / 70%
Alarm if threshold is overrun.
Autres choix
Commentaires
Disabled
Disabled
The UPS restarts automatically
when AC power returns.
Enabled
When function enabled, battery
shuts down when power drops to
<5%.
Enabled
When function enabled, the UPS
remains OFF if the system detects
phase/neutral inversion.
Other available settings
Comments
No test / daily test /
monthly test
0 to 100%
Adjustable in 1% steps.
13 to 200 Ah
Disabled
When function disabled, EATON
warranty no longer applies.