Dimensions; Minimum Clearances; Dimensions Minimum Clearances; Combiplus Installation Options - Viessmann Vitodens 100-W WB1B Series Installation And Service Instructions Manual

Vitodens 100-w wb1b series wall-mounted, gas-fired condensing boiler with optional on demand hot water combiplus kit
Table of Contents

Advertisement

Dimensions

Minimum Clearances

Front
1
*
Refer to the Installation Instructions of the Vitodens
Venting System for details.

CombiPLUS Installation Options

Shown is the distance between the boiler and CombiPLUS
with Viessmann supplied 7" flex piping connection fittings.
Note: The maximum distance between
the boiler and the CombiPLUS
is restricted by the communication
cable to 36" (915 mm).
10
Side
Top *
Back
Side
5
Vitodens 100-W, WB1B Installation & Service
Recommended minimum service clearances
Note:The Vitodens 100-W boiler has passed the zero
inches vent clearance to combustibles testing
requirements dictated by the boiler Harmonized
Standard ANSI Z21.13. CSA 4.9.2007 and
therefore is listed for zero clearance to combustibles
when vented with a single-wall special venting
system (AL-29-4C material) or UL/ULC-listed CPVC
gas vent material. The zero inches vent clearance
to combustibles for the Vitodens 100-W boiler
supercedes the clearance to combustibles listing
that appears on the special venting system label.
Top clearance - 12" (30 cm).
See the Vitodens Venting System
Installation Instructions.
Clearance to combustibles
Top
Front
0
0 AL,
CL
AL = Alcove
CL = Closet
Shown is the maximum distance between the boiler
and CombiPLUS using field supplied fittings and pipes.
Rear
Left
Right
0
0
0
Vent
pipe* 1