Checking Or Replacing The Plate Typeheat Exchanger - Viessmann Vitodens 100-W WB1B Series Installation And Service Instructions Manual

Vitodens 100-w wb1b series wall-mounted, gas-fired condensing boiler with optional on demand hot water combiplus kit
Table of Contents

Advertisement

Vitodens 100-W, WB1B Installation & Service
CombiPLUS Connection
Checking or replacing the plate type heat exchanger
Legend
A Three-way valve drive
B Three-way valve
C Screws
D Plate-type heat exchanger
E Heating water supply
F Heating water return
G DCW
H DHW
(continued)
1. Shut off and drain the boiler on the heating water
2. Disconnect diverting valve motor connection
3. Push the three-way drive A slightly upwards.
4. Turn the three-way valve B with drive A 1/8 turn
5. Remove two screws C from the plate-type heat
6. Check the DHW side for scaling and if required, clean
7. Check the heating water side for contamination
8. Install in reverse order with new gaskets.
To remove,
push to
unlock
and the DHW side.
counterclockwise and remove.
exchanger and remove the plate-type heat exchanger
D with gaskets.
Note: During removal, small amounts of water may
trickle out and escape from the removed plate-
type heat exchanger.
or replace the plate-type heat exchanger.
and if required, clean or replace the plate-type heat
exchanger.
Note: Refer to the installation Instructions for
additional mounting options.
Troubleshooting