IFS-2600 Installation & Programming Manual

Supply Fan Connection Diagram

1
A
AUX POWER
AUX +24
AUX 0V
FAN START RELAY
(MAPPED TO ACF FOR
GENERAL OR ZONED)
FAN STOP RELAY
(MAPPED TO AIR INTAKE
SMOKE DETECTOR)
B
* NOTE
EITHER THE MAPPING ABOVE MAY
BE USED TO START THE SAF
OR THE GENERAL ACF TRIP BELOW,
BUT NOT BOTH.
USE OF THE FIRE TRIP RELAY BELOW
REQUIRES THAT THE MSSB
STARTS THE FAN.
C
FROM FIP
+24
ACF
0v
D
No.
Revision - revise on CAD. Do not amend by hand Eng.
1
P/N 10069 ECN08-0066
2
FIRE PANEL
FAN TERMINATION BOARD
+24
0V
START1
STOP1
PCB1128
Copyright
This document is & shall
remain the property of
O
Notifier Inertia Fire Systems
C
Unauthorised use of this
document in any way is
prohibited.
Drawing File No.
App.
Date
=DocumentFullPathAndName
2
3
+24
COMMON +VE
START
START
CONTROL
STOP
RUN
STOP
INDICATION
FLT
FAN 1
RUN
STOP
FAULT
AUTO
OFF
ON
FRONT PANEL CONTROL
7 Columbia Court,
Norwest Business Park
Baulkham Hills NSW 2153
AUSTRALIA
Tel
61 2 9894 1444
Fax
61 2 9899 4156
Email: support@inertia.com.au
3
FIELD WIRING
STOP
FAN RUNNING
FAN STOPPED AND POWER AVAILABLE
FAN FAULT OR NO POWER AVAILABLE
* NOTE
THE MECHANICAL SERVICES BOARD
MUST BE CONFIGURED TO HAVE
THE STOP RELAY TO TAKE
PRECEDENCE OVER THE START RELAY
+
+
LOAD
IN
-
-
+
D1
OUT
-
R1
FIRE TRIP
PCB1125
RELAY
Title
Sheet:
1
Of:
1
SUPPLY AIR FAN (TYPICAL)
Drawn/
Engineer
19/8/05
I PERRY
Traced
Design
Approved
Drg.
Size
A4
This Drawing must not be used for Construction
No.
unless signed as approved
Page 65
4
A
B
C
D
CONTROL
Rev
2600-SAF