Auto Change Over Dual Sounder Connection Diagram - Honeywell NOTIFIER IFS-2600 Technical Installation Manual

Fire indicator panel
Table of Contents

Advertisement

Page 60

Auto Change Over Dual Sounder Connection Diagram

1
A
IFS2600
TERMINATION
PCB2004
N/O
ALERT ACTIVATION
B
+24
0V
+24
0V
+24
0V
+24
0V
C
NC
COM
IFS803
RELAY
NO
BOARD
EVAC ACTIVATION
D
No.
Revision - revise on CAD. Do not amend by hand Eng.
1
P/N 10069 ECN08-0066
2
IFS958 RELAY BOARD
WARN SYS EOL
Copyright
This document is & shall
remain the property of
O
Notifier Inertia Fire Systems
C
Unauthorised use of this
document in any way is
prohibited.
Drawing File No.
App.
Date
=DocumentFullPathAndName
2
3
NOTE:
REMOVE LINK JP1 FOR MANUAL
CHANGEOVER FROM ALERT TO EVAC
MONITORED DRIVER BOARD
IFS 993
+24V
RED
4K7
7 Columbia Court,
Norwest Business Park
Baulkham Hills NSW 2153
AUSTRALIA
Tel
61 2 9894 1444
Fax
61 2 9899 4156
Email: support@inertia.com.au
3
IFS-2600 Installation & Programming Manual
NOTE:
Maximum capacity is 10 sounders
or 4 strobes
ALERT STROBE
EVAC STROBE
(AMBER)
(RED)
0V
+24V
0V
BLACK
RED
BLACK
4
3
2
1
4
DUAL TONE AS2220
DUAL TONE AS2220
SOUNDER
SOUNDER
Title
IFS2600 MONITORED
Sheet:
1
Of:
1
DUAL SOUNDER
Drawn/
Engineer
23/8/05
I PERRY
Traced
Design
MANUAL CHANGEOVER
I PERRY
Approved
Drg.
Size
A4
This Drawing must not be used for Construction
No.
unless signed as approved
4
A
B
1K8
EOL
C
3
2
1
D
Rev
2600-DUAL
A
MANUAL-SNDR
4

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents