Dk, R1, R2 Cooling Coil Data - Trane HUV Installation Operation & Maintenance

Classroom unit ventilators
Table of Contents

Advertisement

Table P11: 4-pipe DK coil, CW cooling data
Unit
Size
Coil
Type
075
100
DK
125
150
200
Table P12: 4-pipe R1, R2 coil, CW cooling data
Unit
Size
Coil
Type
R1
075
R2
R1
100
R2
R1
125
R2
R1
150
R2
R1
200
R2
7 6
Performance Data
DK, R1, R2-Coil Cooling
Cooling (80 EDB/67 EWB, 45 EWT/55 LWT)
TMBH
SMBH
GPM
16.60
13.30
3.33
24.70
18.30
4.94
34.00
24.50
6.79
39.40
27.70
7.87
45.24
33.11
9.04
Cooling (80 EDB/67 EWB, 45 EWT/55 LWT)
TMBH
SMBH
GPM
25.19
17.89
5.04
28.08
19.79
5.62
35.52
24.60
7.10
39.29
27.12
7.86
41.75
29.61
8.35
46.73
32.88
9.35
52.11
36.32
10.42
58.02
40.24
11.60
62.79
44.78
12.56
71.72
50.61
14.34
WPD
1.30
3.10
6.30
9.20
11.83
WPD
3.82
4.62
8.40
10.04
4.85
5.93
8.11
9.82
11.32
14.37
UV-PRC001-EN

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vuv

Table of Contents