Table P10: 2-pipe, CW cooling data
Unit
Size
Coil
Type
X1
075
X2
X3
X1
X2
100
X3
X1
125
X2
X3
X1
150
X2
X3
X1
200
X2
X3
UV-PRC001-EN
Performance Data
X-Coil Cooling
Cooling (80/67 EAT, 45 EWT/55 LWT)
TMBH
SMBH
GPM
25.20
17.50
5.04
25.20
17.50
5.04
25.20
17.50
5.04
34.90
23.70
6.98
34.90
23.70
6.98
34.90
23.70
6.98
37.50
26.80
7.50
37.50
26.80
7.50
37.50
26.80
7.50
49.50
33.80
9.91
49.50
33.80
9.91
49.50
33.80
9.91
68.55
48.58
13.71
68.55
48.58
13.71
68.55
48.58
13.71
WPD
3.80
3.80
3.80
8.10
8.10
8.10
7.50
7.50
7.50
7.40
7.40
7.40
13.25
13.25
13.25