Parameters/Address Space; Measurement Types And Measuring Ranges - Siemens 181 Workshop Manual

Analog input module ai 4xrtd/tc 2-/3-/4-wire hf (6es7134-6jd00-0ca1)
Table of Contents

Advertisement

Parameters/address space

4.1

Measurement types and measuring ranges

The following table describes the measuring range and the temperature coefficients you can
configure for each measurement type:
Table 4- 1
Measurement types and measuring ranges
Measurement type
Deactivated
Resistor (2-, 3-, 4-wire connection)
Resistor (2-wire connection)
Thermal resistor RTD
(3-wire connection)
Thermal resistor RTD
(2, 3, 4-wire connection)
Thermocouple (TC)
Voltage
The preset temperature coefficients are valid for Europe.
1
For sensors LG-Ni 1000 from Siemens Building Ltd (Landis & Stäfa).
2
Analog input module AI 4xRTD/TC 2-/3-/4-wire HF (6ES7134-6JD00-0CA1)
Manual, 02/2014, A5E03573289-AD
Measuring range
150 Ω / 300 Ω / 600 Ω /
3 kΩ / 6 kΩ
PTC
Climatic / Standard
Cu 10
Climatic / Standard
Pt 100
Pt 200
Pt 500
Pt 1000
Climatic / Standard
Ni 100
Ni 120
Ni 200
Ni 500
Ni 1000
Climatic
/ Standard
2
2
Ni 1000
Type E, N, J, K, L, S, R,
B, T, C, U, TXK (acc. to GOST)
±50 mV / ±80 mV /
±250 mV / ±1 V
Temperature coefficient
Cu 0.00427
1
Pt 0.00385 /
Pt 0.003916 /
Pt 0.003902 /
Pt 0.00392 /
Pt 0.00385055
Ni 0.00618 /
Ni 0.00672
Ni 0.005
4
13