Siemens 181 Workshop Manual page 52

Analog input module ai 4xrtd/tc 2-/3-/4-wire hf (6es7134-6jd00-0ca1)
Table of Contents

Advertisement

Measurement
Measuring
type
range
Thermal
Cu 10
resistor
climatic
(3-wire
connection)
Cu 10
standard
Thermocoupl
Type B, N,
e
E, R, S, J,
L, T, K, U,
C, TXK
x = property is allowed, – = property is not allowed, * = property is not relevant
Use of the "Reference channel of the module":
1
- Channel 0 must be set to "Pt100 climatic" with the temperature unit "Degrees Celsius".
- For each TC channel of this module that is intended to use channel 0 as reference, "Reference junction" must be set to
"Enable".
Use of "Reference channel of group 0":
2
- An RTD channel must be set as "Pt100 climatic" with temperature unit "Degrees Celsius".
- "Reference channel of group 0, 1, 2, 3" must be set as the "Reference junction" of this channel.
- There may be only one RTD channel with "Reference junction active" = "Enable" per group and row.
- For each TC channel of this row that is intended to use this reference, "Reference junction active" must be set to
"Enable".
Underflow = 8000
; wire break and overflow lead to 01
3
H
therefore not relevant.
Analog input module AI 4xRTD/TC 2-/3-/4-wire HF (6ES7134-6JD00-0CA1)
Manual, 02/2014, A5E03573289-AD
Temperature
Slot
coefficient
reference
junction
Cu 0.00427
No
reference
channel
mode
Cu 0.00427
No
reference
channel
mode
*
Reference
channel of
the module
Internal
reference
junction
Reference
channel of
group 0, 1,
2, 3
2
Fixed
reference
temperature
A.1 Dependencies when configuring with GSD file
Temperature
unit
Underflow
/ overflow
Degrees
x
Celsius
Degrees
Fahrenheit
Degrees
x
Celsius
Degrees
Fahrenheit
Kelvin
Degrees
x
Celsius
1
Degrees
Fahrenheit
Kelvin
Degrees
x
Celsius
Degrees
Fahrenheit
Kelvin
(triggered) → (no diagnostics), wire break and overflow are
H
Parameter data record
Diagnostics
Wire
Missing
Reference
break
supply
junction
voltage
L+
x
x
x
x
x
x
x
x
x
*
51