Parameter Data Record; Dependencies When Configuring With Gsd File - Siemens 181 Workshop Manual

Analog input module ai 4xrtd/tc 2-/3-/4-wire hf (6es7134-6jd00-0ca1)
Table of Contents

Advertisement

Parameter data record

A.1

Dependencies when configuring with GSD file

When configuring the module with a GSD file, remember that the settings of some
parameters are dependent on each other.
Configuring with a PROFINET GSD file
The table lists the properties and their dependencies on the measurement type and
measuring range for PROFINET.
Table A- 1
Dependencies of the measurement type / measuring range
Measurement
Measuring range
type
Deactivated
*
Voltage
±50 mV, ±80 mV,
±250 mV, ±1 V
Resistor
150 Ω, 300 Ω,
(2, 3, 4-wire
600 Ω, 3 kΩ, 6 kΩ
connection)
Resistor
PTC
(2-wire
connection)
Thermal resistor
Pt100 climatic
(2, 3, 4-wire
connection)
Pt200
Pt500
Pt1000 climatic
Ni100
Ni120
Ni200
Ni500
Ni1000 climatic
LG-Ni 1000
climatic
Analog input module AI 4xRTD/TC 2-/3-/4-wire HF (6ES7134-6JD00-0CA1)
Manual, 02/2014, A5E03573289-AD
Temperature
Reference junction Temperature unit
coefficient
*
*
*
*
*
*
*
*
Pt 0.00385055
Reference channel
Pt 0.003916
of group 0, 1, 2, 3
Pt 0.003902
No reference
Pt 0.00392
channel mode
Pt 0.00385
No reference
channel mode
Ni 0.00618
Ni 0.00672
LG-Ni 0.005
Conductor
resistance
*
*
*
*
*
x (with 2-wire
connection)
*
*
Degrees Celsius
x (with 2-wire
connection)
Degrees Celsius
Degrees
Fahrenheit
Degrees Celsius
Degrees
Fahrenheit
A