Technical data

Power supply (not provided)
Input
Output
Cable between power supply and Connect Box
Internal protection

Function data

Hardware information
Processor
Operating system
Storage
Interfaces
Ethernet interface
Plug
Interface type
Bit rate
Protocol
Cabling (in-house cabling only), cable type
Cable length
Modbus RTU interface
Interface type
Baud rate
Bus termination
Internal bus polarization
Cabling (in-house cabling only)
Cable length
Protection
Smart Infrastructure
Smart Infrastructure
AC 85-264 V
DC 24 V ±10 %, min. 2 A
2 wires (red, black)
22 AWG , minimum section: 0.35 mm
Protection against overvoltage, undervoltage, and
overcurrent from the power supply with indication by
LED: green LED when the power supply is compatible,
red LED if it is not suitable.
ARM Cortex A7, 528 MHz
Linux
512 MB RAM
4 GB Flash
2 x RJ45, shielded
10Base-T / 100Base-TX, IEEE 802.3 compatible
10/100 Mbps, autosensing
BACnet/IP on UDP/IP, BACnet/SC on TCP/IP, and
HTTPS on TCP/IP
10 Mbps: Min. CAT3, shielded cable is recommended
100 Mbps: Min. CAT5, shielded cable is recommended
Max. 100 m (330 ft)
EIA-485, not isolated
300, 600, 1200, 2400, 4800, 9600, 19200, 38400,
57600, 76800, 115200 (depending on the configuration)
120 Ohm to be added on connector by the integrator on
the bus (both ends of the bus)
No
3-wire cable, shielded cable recommended (shield must
be connected to building earth in the mounting panel)
Short-circuit protection with resettable fuse
-7 V to +12 V common-mode
Up to 15 V overvoltage protection
2
7
A6V13605540_en--_b
2022-10-14