G. Mantel
Refer to the shaded areas of Figure 9.3 for the location and dimensions of a combustible mantel.
A combustible mantel may be positioned no lower than 22 in. (508 mm) above the top of the fireplace opening.
A combustible mantel may have a maximum depth of 12 in. (305 mm).
Combustible trim and materials cannot be placed within 6 in. (152mm) of the fireplace opening (top or sides).
Combustible materials projecting more than 1 1/2 in. (38 mm) shall not be placed within 12 in. (305 mm) from the top of
the fireplace opening.
Combustible trim must not cover the metal surfaces of the fireplace.
Mantel clearance is in accordance with Section 7-3.3.3 of ANSI/NFPA211.
Figure 9.3 Clearance to Mantel or other non-combustilbes above fireplace
26
Outdoor Lifestyles by Hearth & Home Technologies Inc. • 4070-300 Rev C • 4/11
Combustible Wall
2 x 4 stud wall
Standoffs
Non-combustible
Decorative Facing
such as:
Steel, iron, brick,
tile, concrete, slate,
glass, plasters.
Seal joint with
non-combustible
sealant
Combustible
Decorative Facing
Grid represents
1 in. squares
12 in./305 mm

Mantel

22 in./559 mm
minimum
12 in./305 mm
minimum
6 in./152 mm
minimum
1 1/2 in./
38 mm
maximum
Measured from top of fireplace opening
7 ft (2134 mm)
minimum
base of fireplace
to ceiling