Introduction; Setup Procedure; Startup Procedure - Omron E5ARER User Manual

Digital controller devicenet communications
Table of Contents

Advertisement

Introduction

2-1

Introduction

2-1-1

Setup Procedure

Step
Item
1
Mount the Digital Controller.
2
Wire the Digital Controller.
3
Turn ON the power to the Digital Con-
troller.
4
Set the DeviceNet node address.
5
Turn OFF the power to the Digital
Controller.
2-1-2

Startup Procedure

Note
Step
Item
6
Connect the DeviceNet com-
munications connector.
7
Turn ON the power to the Digi-
tal Controller.
8
Turn ON the DeviceNet com-
munications power (V+, V
9
Check the MS/NS indicators
2-2
Use the procedures in the following sections to prepare the E5AR/ER-DRT
Digital Controllers for use. Refer to the following reference pages/sections
provided for detailed information on each step.
Mount the Digital Controller to the panel.
Wire the temperature inputs and control outputs to the Digital
Controller terminals.
Note Do not turn ON the power supply to the peripheral
devices at this time.
Turn ON the power connected to the Digital Controller.
Note The Digital Controller will start.
Set the DeviceNet node address (0 to 63) for the Digital Con-
troller on the front panel. Set a unique node address for each
slave connected to the same master.
Turn OFF the power connected to the Digital Controller.
Prepare the master, DeviceNet communications power supply, and Configura-
tor that will be used in the system. Use the Configurator to allocate Digital
Controller data in the IN and OUT Areas. Refer to the DeviceNet Operation
Manual (W267) for information on related connection devices.
Up to 100 words each can be allocated in the IN Area and OUT Area for
remote I/O communications. To read and write larger amounts of data, use
explicit messages. Use explicit message communications also for reading and
writing data only when required.
Connect the DeviceNet communications connector.
Note Do not turn ON the communications power supply at
this time. This power supply is also used as the inter-
nal circuit power supply for DeviceNet communica-
tions.
Turn ON the power connected to the Digital Controller.
Note The Digital Controller will start.
Turn ON the communications power supply to DeviceNet.
).
Note The DeviceNet communications will start.
Check that the status of the MS and NS indicators is as fol-
lows:
MS: Operating normally when lit green.
NS: Operating normally when lit green.
(DeviceNet online or communications connected.)
Details
Details
Section 2-1
Reference
page 3-4
page 3-10
page 3-10
page 2-3
---
Reference
page 3-15
page 3-10
---
page 3-3

Advertisement

Table of Contents
loading

This manual is also suitable for:

E5arE5er

Table of Contents