Gas Conversion Kit Gas Conver- sion Instruc- tions For models: B34-DV-2 C34-DV C38-DV C42-DV ME34-DV-2 MD34-DV-2 ME38-DV-2 MD38-DV-2 Warning: If the information in these instructions is not followed Check local codes and ...
This gas conversion kit contains the necessary components for field General Information ..............2 conversion of an approved Montigo fireplace from Natural Gas (NG) Parts list ..................2 to Liquid Propane (LP).This kit is approved for use with the following...
Page 3
Gas Conversion Kit Gas Conversion Instructions Conversion CAUTION - Before you begin: Rear Burner: Shut off gas at the shut-off valve and disconnect the electrical Remove the screw that secures the left end of the burner to the supply (if used). firebox.
Gas Conversion Kit Gas Conversion Instructions Checking the Gas Pressure Re-install the rear burner and ensure that the pilot burner is To check the Inlet and Manifold gas pressures, a Water Column Pres- correctly positioned. The pilot and burner should be replaced sure Gauge with 5/16"...
Gas Conversion Kit Operating Instructions For Your Safety - READ BEFORE LIGHTING: WARNING: If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or loss of life. A. This appliance has a pilot. When lighting the pilot, follow If you cannot reach your gas supplier, call the Fire De- ...
Page 6
Gas Conversion Kit XG0668 Rev. 00 - 07/02 Montigo Del Ray Corp. Canadian Heating Products Inc. Ferndale, WA 98248 Langley, BC V4W 4A1 Page P/N XG0668...