Toshiba T-PSV Operation Manual page 36

Programmable controller prosec t-series dde server
Table of Contents

Advertisement

Message
The number of Continuous Register
Tags in High-speed cycle exceeds 248
registers. (1 double-word Tag requires
2 registers)
The number of Continuous Register
Tags in Low-speed cycle exceeds 248
registers. (1 double-word Tag requires
2 registers)
The number of Continuous Register
Tags in Middle-speed cycle exceeds
248 registers. (1 double-word Tag
requires 2 registers)
The number of PLC setting for the
[Connection Name] exceeds the
maximum. (MAX.64 for each
connection.)
The number of TAGs exceeds the
maximum.(Max.4096 in total).
Timeout is out of allowable range.
Timeout must be 0.1 increments.
Timeout value must be numerical
value.
Total connection must be 2 or less.
Update Cycle is out of allowable range
(High-speed/ Middle-speed/Low-speed).
Update Cycle must be 0.1 increments
(High-speed/Middle-speed/Low-speed).
Windows socket initialization failure.
In the Tag setting, the number of registers for a PLC per High-
speed update cycle exceeds 248. (Continuous address Tag)
One double-word Tag requires two registers. The maximum
number of registers available in 1 PLC is 248 words per each
update cycle.
In the Tag setting, the number of registers for a PLC per Low-
speed update cycle exceeds 248. (Continuous address Tag)
One double-word Tag requires two registers. The maximum
number of registers available in 1 PLC is 248 words per each
update cycle.
In the Tag setting, the number of registers for a PLC per
Middle-speed update cycle exceeds 248. (Continuous address
Tag)
One double-word Tag requires two registers. The maximum
number of registers available in 1 PLC is 248 words per each
update cycle.
In the configuration file, the number of PLCs for one
connection exceeds 64.
Reduce the PLCs.
In the configuration file, more than 4096 Tags are designated.
The maximum number of Tags is 4096.
In the connection setting, timeout setting is more than 65.5
sec.
Set the timeout within the range of 0.2 to 65.5 sec.
In the connection setting, timeout setting is not 0.1 increments.
Set the timeout correctly.
In the connection setting, timeout setting contains other than
number.
Set the timeout correctly.
In the configuration file, more than two (2) connections are
designated.
One Ethernet and one serial are maximum connections.
In the connection setting, update cycle setting is more than
65.5 sec.
Set the update cycle within the range of 0.2 to 65.5 sec.
In the connection setting, update cycle is not 0.1 increments.
Set the update cycle correctly.
It failed to initialize the socket service.
Check Windows network setting. TCP/IP protocol must be
installed.
6. List of Error Messages
Contents
Operation Manual
35