Advertisement

4. Configuration File

4.2 Inside the configuration file

The configuration file contains the connection, PLC, and Tag settings.
The first column of each line designates the setting ID as follows.
Setting ID (first column):
Comment line
Connection setting
Serial setting
PLC setting for Ethernet
PLC setting for Serial
Tag setting for individual address
Tag setting for continuous address (Staring)
Tag setting for continuous address (Following)
The setting line order should be as follows.
C (Connection setting) ... Ethernet or serial, update cycle setting, etc.
--- If above line is for Ethernet ---
PE (1st PLC on Ethernet) ... IP address, port number, PLC model, etc.
T/TA (1st Tag of 1st PLC) ... Tag name, corresponding PLC register/device, update cycle, etc.
T/+ (2nd Tag of 1st PLC) ... Ditto
:
PE (2nd PLC on Ethernet) ... IP address, port number, PLC model, etc.
T/TA (1st Tag of 2nd PLC) ... Tag name, corresponding PLC register/device, update cycle, etc.
T/+ (2nd Tag of 2nd PLC) ... Ditto
:
C (Connection setting) ... Ethernet or serial, update cycle setting, etc.
--- If above line is for serial ---
CS (Serial setting) ... COM port number, baudrate, parity, etc.
PS (1st PLC on serial line) ... PLC station address, PLC model, etc.
T/TA (1st Tag of 1st PLC) ... Tag name, corresponding PLC register/device, update cycle, etc.
T/+ (2nd Tag of 1st PLC) ... Ditto
:
PS (2nd PLC on serial line) ... PLC station number, PLC model, etc.
T/TA (1st Tag of 2nd PLC) ... Tag name, corresponding PLC register/device, update cycle, etc.
T/+ (2nd Tag of 2nd PLC) ... Ditto
:
18
DDE Server T-PSV
#
C
CS
PE
PS
T
TA
+