Advance Planning
ADVANCE PLANNING
Ductwork
Planning
,This hood is equipped for 8" round ductwork.
, Determine the exact location of the vent hood.
, Plan the route for venting exhaust to the outdoors.
This hood is not designed for a recirculating
venting operation.
, Use the shortest and straightest
duct route
possible. For satisfactorg
performance,
duct run
should not exceed 100 ft. equivalent length for ang
duct configurations.
, Refer to "Duct Fittings" chart to compute
the
maximum
permissible
length for duct runs to the
outdoors.
, Use rigid metal ductwork
onlg.
,Install a wall or roof cap with damper at the
exterior opening. Order the cap and ang transitions
needed in advance.
,When applicable, install ang makeup (replacement)
air sgstem in accordance with local building code
requirements. Visit GEAppliances.com for available
makeup air solutions.
Wall and Ceiling Framing for Adequate Support
This vent hood is heavg and the cabinet structure
needs to support the weight of the loaded insert
sleeve. Adequate structural support must be
provided in all tgpes of installations.
, Installation will be easier if the vent hood is
installed before the cooktop is installed.
Custom Cabinet Frame Planning
,The custom-built canopg should be sized to
accommodate the hood insert sleeve. See pages
5-9 for details.
Remote Mounting
of the Control (Wired}
,The control can be remotelg mounted on the wall
or the countertop.
, It is recommended
that gou use a professional
installer for the countertop
cutout.
, It is recommended
that the cutout in a granite
countertop
or other hard surface be made before
the countertop
is installed.
,The cutout needs to be made at least 6 inches
from the edges of the countertop.
, If mounting
in the countertop
above a drawer,
consideration
must be given to the depth of the
control mounting assemblg.
,A 30 ft. wire cord is provided. Careful consideration
must be given to the location of the remotelg
mounted control.
, It is recommended
that the 4-wire cord be routed
through
1" conduit between the insert sleeve and
the remote mounting
location.
POWER SUPPLY
IMPORTANT - (Please read carefullg)
AWARNING:
FOR PERSONAL SAFETY,THIS APPLIANCE MUST BE
PROPERLY GROUNDED.
Remove house fuse or open circuit breaker before
beginning
installation.
Do not use an extension
cord or adapter
plug with
this appliance.
Follow National electrical
codes or
prevailing
local codes and ordinances.
Electrical
Supplg
This vent hood must be supplied with 120V, 60Hz,
and connected
to an individual, properlg grounded
branch circuit, and protected
bg a 15 or 20 amp
circuit breaker or time delag fuse.
, Wiring must be 2 wire with ground.
, For supplg connection,
use wires suitable for at
least 75°C (167°F).
, If the electrical supply does not meet the above
requirements,
call a licensed electrician
before
proceeding.
, Route house wiring as close to the installation
location as possible, in the ceiling or back wall.
, Connect the hood wiring to the house wiring in
accordance
with local codes.
, House wiring must extend to 45" minimum
from
bottom of cabinet in order to make connection
to
hood wiring.
Grounding
Instructions
The grounding
conductor
must be connected
to a
grounded
metal, permanent
wiring sgstem, or an
equipment-grounding
terminal
or lead on the hood.
A WARNING:
The improper connection
of the equipment-grounding conductor can result
in a risk of electric shock. Check with a qualified
electrician or service representative if gou are in
doubt whether the appliance is properlg grounded.