Table Of Functions And Indications On Control Panel - GE LP 33U Series Operating Manual

50 & 60 kva
Table of Contents

Advertisement

5.2

TABLE OF FUNCTIONS AND INDICATIONS ON CONTROL PANEL

Key to switch the Inverter ON ( I )
Key for Inverter shutdown ( O )
Press key to transfers the Load to Utility.
Keep pressed for 5 seconds to shutdown the Inverter.
This key is also used as the EPO (Emergency Power Off) reset.
Key "Total Off"
The key "Total Off" is protected by a transparent cover.
By pressing it, you immediately separate the UPS from the Load.
It is possible to activate the command "Total Off" using the following screen:
COMMANDS / REQUEST TOTAL OFF. See Section 6.5.
Attention:
To reset "Total Off"
Restore the command "Total Off"
by entering the screen:
COMMANDS / RESET TOTAL OFF
the parallel bus (switch Q1 closed), all the units are separated from the load.
The "Total Off" reset must be done only on one unit connected to the parallel bus
(switch Q1 closed).
Modifications reserved
OPM_LPS_3UO_50K_60K_1US_V010.doc
"TOTAL Off" cannot disconnect the UPS from the Load with Q2 closed.
For Parallel System: if "Total Off" is pressed on one unit connected to
NOTE !
Special care must be taken in using this command, in order to
avoid accidental load disconnection.
Home\Commands
COMMANDS
RESET TOTAL OFF
REQUEST TOTAL OFF
Operating Manual LP 33U Series 30 & 40 kVA
Page 21/65