3-WIRE
SERVICE
CORD
OR CONDUIT
INSTALLATION
1. Insure that the copper ground strap IS CONNECTED
between the middle post of the main terminal
connection block and the range chassis.
.
The middle wire of the service cord or ground lead of
3-wire conduit MUST connect to the neutral (middle)
post of the main terminal block. The other two wires of
the service cord or conduit connect to the outside
posts of the main terminal connection block. Polarity is
unimportant.
A appropriate strain relief for service cord or conduit
must be attached to the conduit plate.
MAIN
TERMINAL
CONNECTION
BLOCK
MIDDLE
WIRE
OF
SERVICE
CORD
OR
GROUND
lEAD
OF
CONDUIT
GROUND
S
(CONNECTED
AI
CONDUIT
FACTORY)
PLATE
S
RELIF
STAMPED
CONDUIT
WITH
CONDUIT.
REMOVE
BRACKET,
FLIP
STAMPED
&
RE-ATTACH
WITH
HOLE
CORD
MARKED
"CONDUIT"
DOWN,
FIGURE 8
ACCEPTABLE
3- WIRE PLUG INSTALLA TION
4-WIRE SERVICE
CORD OR CONDUIT
INSTALLATION
(MOBILE HOMES OR AS REQUIRED BY CODES)
1. The copper ground strap connected between the
neutral (middle) post of the main terminal block and the
chassis MUST be cut off as shown in figure 9. Save the
green ground screw to attach the ground from the 4
wire cord. Only a 4 wire cord or conduit should be
used.
.
The ground wire from the service cord or conduit must
connect to the range chassis using the green ground
screw.
3. The white wire of the service cord or conduit must
connect to the neutral (middle) post of the main
terminal block. The other two wires of the service cord
or conduit connect to the red and black posts of the
main terminal block, respectively.
4. An appropriate strain relief for service cord or conduit
must be attached to the conduit plate.
CONVERSION
FROM
3-WIRE
TO 4-WIRE
SERVICE
(Model With 3-Wire Service Cord Attached)
Disconnect range from power. Remove the access cover
on back of range and remove the 3-wire service cord from
the main terminal block. Follow instructions as outlined in
figure 9 to connect the 4-wire service cord.
NOTE: Cord replacement - ONLY a power supply cord
rated at 240 volts minimum, 40 amperes or 50 amperes
power supply cord that is marked for use with nominal
1 3/8" (34.93 mm) diameter connection opening, with
closed loop terminals and marked for use with ranges
shall be used.
RED -
WHITE-_
MAIN
TERMINAL
BLACK-_/'_
CONNECIIONBLOCK
_/WHITE
WIRE
RVICE
CORD
CONDUIT
kJ_/'_f
CONDUIT
CHASSIS
_P
AIE
GROUND
STRAIN
RELIEF
/J
THIS
PORTION
OF--...
/
GROUNDING
STRAP
"_
/
MUST
BE
REMOVED.
\
\
J
J
t
'\
/
CHASSIS
GROUND
STAMPED
CONDUIT
USE
WITH
CONDUIT,
REMOVE
BRACKE/,
FLIP
& RE-ATTACH
WI_H
HOLE
MARKED
"CONDUI-"
DOWN.
STAMPED
CORD
FIGURE 9
ACCEPTABLE 4- WIRE PLUG INSTALLA TION