Installation; Mounting Heights - Jenn-Air UXT5230AD Series Installation Manual

Hide thumbs Also See for UXT5230AD Series:
Table of Contents

Advertisement

INSTALLATION
MOUNTING HEIGHTS
9B"
36,,
Minimum mounting height between r ange top
tohood bottom sh_ld benolessthan24",
Maximum mounting height should b e nohigh-
erthan32".
itisimportant toinstall thehood at the
proper mounting height. H oods m ounted too
lowcould result i nheatdamage a ndfire
hazard', while hoods mounted toohigh willbe
hard toreach andwilllose performance
and
efficiency.
if available, a lsorefer to range manufacturer's
heightclearance requirements a ndrecom-
mendedhoodmounting heightaboverange.
DUCTING
A minimum of6"round or3-1/4"x10" r ectangular
ductmust b eused tomaintain m aximum airflow
efficiency.
Always userigid-type metalductsonly.
Flexible ductscouldrestrict air flow by up to 50%,
Alsouse calculation (onright) to compute total
availableduct run when usingelbows,transitions
andcaps.
ALWAYS, when possible, reduce thenumberof
transitions andturns.If longductrun is required,
increase duct s izefrom6"to 7 or 8". If a reducer
is used, i nstalla longreducerinstead ofa pancake
reducer. Reduce duct sizeasfarawayfromopen-
ing aspossible.
if turnsortransitions a rerequired:
Install a sfar away fromopening andasfar
apart,between 2 ,aspossible.
DuctRunCalculation:
Maximumrun
6" or 3-1/4" x 10" duct
IOOR"
Deduct:
each90 Elbowused
15 FT
each45 elbowused
9 FT
each5" to 3/14 x 10"
transitionused
1 FT
each3/14 x lO"to 6"
each 3/14 x 10"to 6"
_ansition used
5 FT
SideVial]Capw/damper
30 FT
RoofCap
30 FT
_-
I mofcap, 2 xgO elbows, 1 45elbow used:
=30' ÷ 30'÷ 9' =69'used, 31" available for straight duct r uns.